Installation
Kinetic MVHR Installation & Commissioning
13
Spigot Installation
Air entry/exit spigots may be fitted on either the top or the side of the unit for vertical or horizontal entry or exit. Attach
the spigots, depending on the space available for the ducting and orientation of the unit. Always fit the blanking caps
to the entry or exit hole not in use to ensure the correct airflow into and out of the unit.
Note: Kinetic Plus E units have spigots suitable for either diameter 150 mm ducting (UK model) or for diameter 180
mm ducting (rest of EU model). The diameter 180 mm spigots come complete with self adhesive foam adaptors to
enable it to be used with either diameter 180 mm ducting or diameter 200 mm ducting. These foam adaptors are to
be fixed to the outside of the spigot for diameter 200 mm ducting.
To move the spigots:
1.
Remove the spigot by unscrewing the screw(s)
securing it to the chassis. Then pull the spigot firmly
from the entry/exit hole.
2.
Remove the blanking cap by unscrewing the screw(s)
securing it to the chassis. Then pull the blanking cap
firmly from the entry/exit hole.
3.
Swap over the spigot with the removed blanking cap.
4.
Insert the spigot into the entry/exit hole and secure
with the retaining screw(s).
5.
Insert the blanking cap into the entry/exit hole and
secure with the retaining screw(s).
N.B. Before finally fixing the unit into position it may be more convenient to make
the electrical connections; including the mains connections and any wiring
for sensor(s) or switch(es).