Installation
Kinetic MVHR Installation & Commissioning
9
4.
Remove the 2 screws and detach the Control
Panel and disconnect the mains lead.
5.
Disconnect the connection looms.
6.
Disconnect all the wiring looms from control panel.
7.
Remove the 2 screws and detach the rear Cable
Inlet Plate.
Note that the grommets shown may be replaced
by easy knock-out positions. If these are required,
ensure that you use a grommet or gland to protect
against potential water ingress.
7.
Re-attach the Cable Inlet Plate on the opposite side of the unit.
8.
Fit the Control Panel on the opposite side of the unit. Taking care to reconnect the 2-way, 3-way and internal
connectors to the control panel before securing the panel to the unit.
9.
Re-connect the mains cable: L, N, E, LS1 and LS2.
11
. Leave the front and rear covers off the unit.
12.
For vertical discharge condensate connection continue on page 10, or for horizontal discharge condensate
connection go to page 11.