Installation Instructions

     

Specifications are subject to change without notice. 

Page 7

sales@simx.co.nz | www.manrose.co.nz 

Distributed by Simx Limited

 

MultiVent Continuous Extract Ventilation

2. RS485 Wired inputs

The RS485 terminals are used to connect compatible sensors and switches. The connection allows sensors be daisy chained to simplify wiring. 
The maximum length of cable run from. The unit is limited to 250m. Once accessories are wired to the unit, they must be paired to the unit to 
function correctly.

LOW VOLTAGE CONNECTIONS

1.  Important

: Use 4-core, low voltage, twisted pair, telecoms type cable for accessories. Accessories are connected via the IO (Input Output) PCB; 

see the Low Voltage Connections diagram in the Main fitting and wiring guide.

Pos/Label Description

Action

A

5V

5V Output, 
Max 250mA

RS485 communication to wired 
accessories. Data connection (B, C) if 
available. The 5V and Ground connections 
are available on all units.

B

A+ Data

C

B-

Data

D

GND Ground

E

COM

Digital input 
common

Go to Boost speed (Min.1V, max. 6V).

The 5V output from the RS485 connection can be 
used as a power supply

F

+

Digital input 2

G

COM

Digital input 
common

Go to Low speed (Min.1V, max. 6V).

The 5V output from the RS485 connection can be 
used as a power supply

H

+

Digital input 1

I

COM

Digital output 
common

Unpowered Boost indicator Switch

(switching 6V 50mA max)

J

+

Digital 

output

 2

K

COM

Digital output 
common

Unpowered LED fault indicator switch

(switching 6V 50mA max)

L

+

Digital 

output

 1

M

+

Analog input 2

0-10V analogue input

Two user settable voltage thresholds with two user 
settable actions. The unit will run at normal when 
supplied voltage is between the two thresholds.

N

GND

Ground

O

+

Analog input 1

P

GND

Ground

Low Voltage Switch’s – Boost & Low Speed

Summary of Contents for MultiVent FAN7453

Page 1: ... FAN7453 is a the MultiVent 3 Room Extract Unit ONLY Details in this Installation Instruction Manual give recommendations to how the centralised extract unit can be combined with other components to make it a complete system See the comprehensive Manrose range of Duct and Grille items to complete the installation A B C D E ØF 330 390 111 250 96 125 Supply Max Operating Temp IP Rating Motor Housing...

Page 2: ...y do not play with the MultiVent continuous extract ventilation system In case of damage to the supply cord switch off the device and do not tamper with it Damaged supply cords must only be repaired or replaced exclusively by the manufacturer or by an appointed representative Failure to comply with the above may endanger the safety of people and cause possible damage to the whole system The unit m...

Page 3: ...n the kit make sure that it is fully extended and not crushed sagging or torn Try to minimize the use of diffusers valves by having similar length duct runs to the inlets The bend radius measured to the inside of the bend should be at least 1x the duct diameter Avoid having any bends filters or other obstructions within 250mm of the fan inlets and outlet Securely mount the unit through the mountin...

Page 4: ...lengths of 125mm aluminium foil ducting for the extraction points Extend the 125mm aluminium foil ducting and slide the spigot collar over the ducting by approximately 150mm Slide the 125mm aluminium foil ducting over the spigot Slide the spigot collar over the ducting pressing it firmly all the way down the spigot clamping the aluminium foil ducting in place on the spigot To prevent the spigot be...

Page 5: ... the 150mm aluminium foil ducting DCT0214 to the 150mm waterproof cowl with mesh DCT3619 and tape it to the spigot From outside of the building cut a 150mm minimum hole in the outside cladding of the home and push the 150mm ducting through the hole Fit the waterproof cowl to the building exterior and then from the roof space pull the ducting taut and tape it off at the 150mm to 125mm reducer Exten...

Page 6: ...nit a delay on timer and an overrun timer can be selected and adjusted in the software using the buttons and screen See Commissioning section on page 10 of this document for details 4 The switched live output 230V AC from any other switch or controller such as a simple latching pullcord or push button switch humidistat or PIR detector can be connected to the LS terminal instead of connecting to a ...

Page 7: ...tion Action A 5V 5V Output Max 250mA RS485 communication to wired accessories Data connection B C if available The 5V and Ground connections are available on all units B A Data C B Data D GND Ground E COM Digital input common Go to Boost speed Min 1V max 6V The 5V output from the RS485 connection can be used as a power supply F Digital input 2 G COM Digital input common Go to Low speed Min 1V max ...

Page 8: ...old The unit will boost when the RH is above the threshold set point Analogue inputs Both analogue inputs have adjustable low and high trigger voltages within the 0 10V range The response to being above or below either of the threshold voltages is user settable Note The display doesn t show a decimal point for example at threshold voltage of 5 2V is displayed as 52 on the unit Digital Inputs The u...

Page 9: ...Switch 1 2 Low boost or purge speed Purge c n Comfort Mode Comfort mode Yes or No No d n Delay On Delay on Yes or No No d10 Delay On Time Delay to boost duration 1 to 60 minutes 10m o n Overrun Overrun Yes or No No o10 Overrun Time Overrun duration 1 to 60 minutes 10m r y Humidity Rapid Rise Rapid Rise Rapid rise Yes or No Yes A n Humidity Ambient Response Ambient response Yes or No No h70 Humidit...

Page 10: ...all power is OFF and ensure that it is electrically safe before starting Wire the 230VAC connections as per the diagram below Wire mains connections from a suitable source lighting circuit or add a new dedicated circuit from an RCD protected 10A MCB with the cable to L live BROWN N neutral BLUE and E protective earth GREEN YELLOW Wire a 230V connection from a switch located in the Bathroom that co...

Page 11: ...n switched on will activate PURGE 100 speed FAULT CODES FOR COMPLIANCE WITH G4 AS1 CLAUSE 1 5 If the MultiVent unit detects a fault it will display an error message on the HMI display These applications are to be installed and maintained to the requirements of AS NZS 3666 1 and AS NZS 3666 2 Fault Code Description F01 Control fault Unit failed startup check F02 Motor Fault No RPM F03 Humidity Temp...

Page 12: ...bly Only the full scroll assembly is replaceable 2 To remove the scroll assembly isolate the power then use a coin or similar to depress the cover retention clips and remove the cover 3 Disconnect and remove the power supply and signal leads 4 Remove the scroll assembly by unscrewing the two screws and unclipping the clips in the opposite two corners and lift the scroll assembly out of the housing...

Reviews: