background image

 

2

 

Installation and Wiring Instructions for the SDX IN-LINE CENTRIFUGAL DUCT FAN range.

 

IMPORTANT: READ THESE INSTRUCTIONS BEFORE COMMENCING THE INSTALLATION

 

 

DO NOT install this product in areas where the following may be present or occur: 

 

Excessive oil or a grease laden atmosphere. 

 

Corrosive or flammable gases, liquids or vapours. 

• 

Ambient temperatures higher than 40°C or less than –5°C. 

• 

Possible obstructions which would hinder the access or removal of the Fan. 

 

Sudden ductwork bends or transformations close to the Fan. 

 

SAFETY AND GUIDANCE NOTES 

 

A. 

All wiring to be in accordance with the current I.E.E. Regulations, or the appropriate standards of your country and 

MUST 

be 

installed by a suitably qualified person. 

B. 

The Fan should be provided with a local double pole isolator switch having a contact separation of at least 3mm. 

C. 

Ensure that the mains supply (Voltage, Frequency, and Phase) complies with the rating label. 

D. 

The Fan should only be used in conjunction with the appropriate Vent-Axia products. 

E. 

It is recommended that the connection to the fan connecter terminals is made with flexible cable. 

F. 

When the Fan is used to remove air from a room containing a fuel-burning appliance, precautions must be taken to avoid 

back-flow of gases into the room from the open flue of gas or other appliance.  Ensure that the air replacement is adequate 
for both the fan and the fuel-burning appliance. 

G. 

The Fan should not be used where it is liable to be subject to direct water spray for prolonged periods of time. 

H. 

Where ducted Fans are used to handle moisture-laden air, a condensation trap should be fitted. Horizontal ducts should be 

arranged to slope slightly downwards away from the Fan. 

I. 

This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, 

or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the 
appliance by a person responsible for their safety. 

J. 

Young children should be supervised to ensure that they do not play with the appliance. 

K. 

Note:- This is a class 1 appliance and MUST be earthed. 

 

A. INSTALLATION. 

The unit is designed as an in-line duct fan to be positioned between lengths of ducting.  Short duct runs terminating close to the 
fan (i.e. within 1.5m) must incorporate suitable guards unless the fan is mounted higher than 2.1m above the floor.   If flexible 
ducting is used it should be fully extended to obtain the best results. Position the fan at the highest point on the system with both 
ducting runs sloping downwards from this point.  In circumstances where an excessive amount of moisture is present in the air 
then a condensation trap should be installed.  When siting the appliance ensure that there is sufficient space to allow access for 
any servicing and maintenance. 
 
Attaching the mounting feet 
Select the image that relates to your fan. 
 
 

 
                                                                                                
 
 

 
 

For horizontal mounting 

For horizontal mounting 

For Vertical mounting 

For Vertical mounting 

Reviews: