Commissioning
Sentinel Kinetic MVHR Installation & Commissioning
33
Cooker Hood Supply Screen
The Cooker Hood Supply screen enables you to set the
Boost speed for the Supply fan.
Default Cooker Hood speed = 100%
Cooker Hood speed cannot be set below Boost speed.
Ckr Hood Supply
100 %
Cooker Hood Extract Screen
The Cooker Hood Extract screen enables you to set
the Boost speed for the Extract fan.
Default Cooker Hood speed = 100%
Cooker Hood speed cannot be set below Boost speed.
Ckr Hood Extract
100 %
Boost Overrun Screen
The Boost Overrun screen enables you to set a time
period for the fans to boost airflow (in minutes) after the
light switch (LS input) is turned off. It will then return to
normal airflow.
Selectable range: minimum =
00,
maximum =
25
,
default =
15
.
Boost Overrun screen does not function for inputs
S/W1 to S/W3 and SW4, SW5
Boost Overrun
15 m
Boost Delay Screen
The Boost Delay screen enables you to set the time
delay (in minutes) from the light switch (LS input) being
switched on to the airflow boost being activated. This is
used to prevent the unit from boosting unnecessarily
when the light switch is switched on for short periods.
Selectable range: min. =
00
, max. =
10,
default =
00
.
Boost Delay
00 m