Internal Timer: VA100SVXHT12 

The fan contains an adjustable overrun timer. Activated by LS.  
 

1. 

Remove the fan grille. The controller is factory set at 15 minutes approx. The overrun time 
period can be adjusted from 3-25 minutes by altering the adjuster on the control PCB. 

2. 

To REDUCE the operating time, use a small screwdriver to turn the adjuster 

ANTI-

CLOCKWISE

3. 

To INCREASE the operating time, use a small screwdriver to turn the adjuster

 CLOCKWISE.

  

4. 

Replace the fan grille. 

 

Humidity Set-Point adjustment (VA100SVLH12 / VA100SVXH12 / VA100SVXHT12)

 

BEFORE ADJUSTING THE HUMIDISTAT, SWITCH OFF THE MAINS SUPPLY. HUMIDISTAT SHOULD 
ONLY BE ADJUSTED BEFORE OR DURING INSTALLATION. 

 

1. 

Remove the fan grille. The controller is factory set to switch on at about 70% RH. The humidity 
set point can be adjusted from 40-95%RH by altering the adjuster on the control PCB. 

2. 

To LOWER the set-point use a small screwdriver to turn the adjuster 

ANTI-CLOCKWISE

. This 

makes the controller MORE sensitive.  

3. 

To RAISE the set-point use a small screwdriver to turn the adjuster 

CLOCKWISE

. This makes 

the controller LESS sensitive.  

4. 

Replace the fan grille. 

 

IMPORTANT: 

Upon installation it is possible that the humidity controller will make the fan run continuously 

until it has acclimatised to the environment. As part of the installation process it is important to set/adjust the 
humidity sensitivity to the desired position. The controller is already factory set to switch on at about 70% R.H. 

 
 

SHUTTER OPERATION 

The shutter mechanism in all VA100‘X’ model fans will open approximately one minute after the fan is turned 
on. The shutter will close about a minute after the fan is switched off. 
 

NEON OPERATION 

The Neon will activate whenever the LS or PULLCORD is activated. The Neon will switch off if the fan is 
running in Timer overrun or humidity mode (if applicable).  

 
PULLCORD OPERATION (VA100SVLH12, VA100SVXH12) 

The PULLCORD will activate the fan when switched. When the PULLCORD is switched into the off position, 
After which the fan will return to the Auto sensing mode.  The Neon will only activate if the PULLCORD is in 
the ON position. 

 
D. SERVICING AND MAINTENANCE. 

 

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM 
THE POWER SUPPLY DURING MAINTENANCE. 

 
1.  At intervals appropriate to the installation, the fan should be inspected and cleaned to ensure there is no 

build up of dirt or other deposits.  

2.  Wipe the inlets and front face with a damp cloth until clean. 
 

The fan has sealed for life bearings, which do not require lubrication. 

 

Fig. 1 

 
 
 

.   

 

 

Summary of Contents for VA100

Page 1: ...2 25 84 10E VA100SVLH12 25 81 12E VA100SVXH12 25 83 12F VA100SVXHT12 25 85 12C PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS VA100 SELV 12 RANGE FAN UNITS 1...

Page 2: ......

Page 3: ...only be used in conjunction with the appropriate Vent Axia products E It is recommended that the connection to the fan connector terminals is made with flexible cable F The transformer controller shou...

Page 4: ...exposed to direct water spray e g from a shower head whether permanently fixed or movable 2 Site away from direct sources of heat Ambient temperature range 0 to 40 C Do not site in an area containing...

Page 5: ...n 4 Repeat for the external grille sub frame Fix exterior grille into position with the louvres positioned downwards AFTER INSTALLATION ENSURE IMPELLER ROTATES FREELY B WIRING WARNING THE FAN AND ANCI...

Page 6: ...sible that the humidity controller will make the fan run continuously until it has acclimatised to the environment As part of the installation process it is important to set adjust the humidity sensit...

Page 7: ...FUSE Switched Fused Spur N 2 1 Controller L Fan SELV Supply 12V 50Hz Pullcord L N 3A UK LS N L N Fan Controller LS L N SELV Supply 12V 50Hz 3A UK Ls LS 0 12V N L 1 Phase Supply 220 240V 50Hz FUSE Swit...

Page 8: ...tact your local supplier Vent Axia guarantees its products for two years from date of purchase against faulty material or workmanship In the event of any part being found to be defective the product w...

Reviews: