13
both internal and external sensor.
04:FR
Antifreeze function. 00=Off, 01=On. If function is on
the antifreeze symbol will be shown in the display. See also
sub-setting 05.
05:FS
Temperature limitations, antifreeze and maximum floor
temperature.
05=Basic antifreeze, the thermostat will start heating if the
temperature goes below 5 degree Celsius.
CU=User defined settings. Minimum limits as set in
sub-setting 06 and 08 will be used for antifreeze purposes. In
addition if both sensors are active (sensor mode 02) the
thermostat will limit the maximum floor temperature (using the
floor sensor max value) according to the value set in
sub-setting 09.
Active sensor according to setting 10:SE will be used for
temperature measurement. If sensor mode=02 the room
(internal) sensor will trigger the antifreeze function.
06:RO
Defines valid minimum setting/value for room
temperature.
07:RO
Defines valid maximum setting/value for room