24
1. Installation of the floor sensor
1.1
The floor sensor shall be positioned centered between two
heating cable strings in the floor
before
pouring concrete
or screed. It is recommended to install the sensor in a
flexible conduit. The conduit should cover the full sensor
length. Seal off the conduit in the (floor) end to prevent
concrete or screed from entering. It is recommended to
position the conduit/sensor as close to the floor surface as
possible (fig. 1)
1.2
Feed the sensor into the conduit so that the sensor itself is
positioned near the end of the conduit in the floor.
1.3
Proceed to section 2.
2. Installation of the thermostat
1.4
Verify that the supplying circuit is completely
disconnected.
1.5
If the heating cables are installed in a wet room (for
example bathroom), the thermostat shall be placed outside
the room. For dry rooms, the thermostat can preferably be
placed inside the room. If the heating cables shall be
Summary of Contents for VAUFHTC