Page 3
L108 1213A
Installation Details
1) Read all instructions thoroughly before beginning installation. Note: These instructions apply to standard liners only.
Custom liners may require additional specification consideration.
2) When installing a SLD wall mount liner (19 1/4” deep), it is recommended that the bottom edge of the liner be located
no more than 24” - 27” above the cooking surface for optimum performance. For PSLD and PSLB wall mount liners (22
1/2” deep), it is recommended that the bottom edge of the liner be located no more than 27” - 30” above the cooking
surface for optimum performance. For custom liners, the recommended height off the cooking surface is dependent
on the depth of the liner. In general, the deeper the custom liner, the higher off the cooking surface it can be, up to a
maximum recommended height of 30”above the cooking surface for optimum performance.
3) Install the duct(s) from the outside of the home down to the location of the exhaust outlet(s) on the top of the liner
allowing room for the transition (if applicable). If back venting, the elbow(s) should be installed so that the non-crimped
end(s) are on the inside the collar(s) of the exhaust outlet(s). If a transition is used, install duct down to the location of
the transition outlet plus 1”. This will allow the transition to engage 1” inside of duct. Consult the connection diagrams
(next page) for further details on exhaust outlet placement.
Use duct tape to seal all joints. A complete listing of available Vent-A-Hood ducting materials is included on the back
page of this instruction sheet.
Transition heights are as follows:
Single Blower (B100):
6” round duct will connect directly to the top of the liner.
Dual Blower (B200):
8” round duct will connect directly to the top of the liner.
Single and Dual Blower (B100 & B200): 6” round duct will connect directly to the top of the hood; 8” round will
connect directly to the top of the hood. Optional 10” round combination
transition (VP562, sold separately) is 17 1/2” tall.
Two Dual Blowers (Two B200s):
Two 8” rounds connect directly to the top of the hood. Optional 12” round
combination transition (VP563, sold separately) is 16 1/2” tall.
SLD Liner
PSLD/PSLB Liner