background image

Page 4

5.0

 INSTALLATION AND WIRING GUIDE

5.1

 

MOUNTING THE CIE EQUIPMENT

Identify a suitable location for mounting the CIE (Control Indicator Equipment) taking into 
consideration the routing of cables and access to the CIE for both installation and user. Remove 
the PCB and keep safe, mark the location of the holes to be drilled by offering the CIE rear 
enclosure to the wall. Drill holes for suitable rawl plugs to provide a strong and secure installation.

2.0

 CONNECTIONS

2.1

 

Terminal Diagrams

2.2  

FIELD CONNECTIONS - TB3 

These terminals provide the outputs to drive the internal and external sounders and strobes. 
There are two separately fused outputs, both circuits are monitored for open and short 
circuits conditions with EOL monitoring resistors (6K8). Sounders must be polarised, fully 
suppressed and designed for 24VDC operation. The total load for both circuits must not 
exceed 750mA. If the sounders or strobes are not polarized a fault will be indicated.  The 
same wiring rules apply as for the detector circuits.

+

BELL 1

-

+

BELL 2

-

REMOTE

RING

The REMOTE RING terminals can be used to force trigger the bell relay without a fire 
condition occurring or operating the auxiliary relay. This gives the ability to wire remote 
evacuation switches. This is NOT a latching trigger and will return to a normal state when the 
connection is broken. Often used as a class change.

C

NO

NC

A

U

X

The CIE is fitted with a double pole auxiliary 1 Amp relay which operates only when a fire 
condition is recognised. The relay does not operate if the manual SOUND ALARM is pressed.

+

BATT

-

These terminals provide connection for a 24V backup battery. 12V batteries are connected in 
series. The 6K8 Ohm resistor must be removed before fitting any battery to this terminal. 
Failure to remove the resistor will not enable the panel to test the batteries health. 

2.3  

KEY SWITCH - TB2

 

KEYSW

These terminals provide the connection for the on board key switch which enables and 
disables the control buttons. When the switch is closed the control buttons are enabled. No 
other connection should be made to these terminals.

2.4  

A/C SUPPLY INPUT - TB1 

A/C

These terminals provide the connection from the on board transformer, which provides 
approximately 32 V ac. No other connection should be made to these terminals

2.5  

INTERNAL BUZZER - TB4 

BUZZER

These terminals provide the connections to supply a wired internal buzzer. These terminals 
are only fitted when the on board buzzer SND1 is not fitted. No other connection should be 
made to these terminals.

+

ZONE 2

-

+

ZONE 1

-

These terminals provide the inputs allowing the connection of smoke heads and alarms 
points to the CIE. All devices must be connected in parallel to the CIE. 22V DC is supplied to 
the zone terminals suppling a maximum current of 50 mA per zone, a 6K8 Ohm end of line 
resistor must be fitted in the further most detection device from the CIE. To produce a fire 
state the detector should draw sufficient current to trigger a fire alarm and have a 470 Ohm 
resistor in series. Not only do the terminals detect a fire state but they offer detection of open 
and short circuit of the cables.

FIRETRAX CIE PANEL

4.11  

REMOTE RING

The connection of a normally open switch to the remote ring terminals, will allow the external sounders to be 
used for ancillary functions  for example 'Class Change.' Multiple switches can be used by connecting the 
switches in parallel.

This work must be carried out by a suitably qualified engineer and installed to the latest mandatory 
Fire Alarm Installation Regulations which are applicable at the time of installation. The correct 
polarity must be observed and a good earth must be used. 

The Fire Alarm system must not share its mains supply with any other electrical circuit and should 
be connected via an isolating protective device and labelled 'FIRE ALARM DO NOT SWITCH 
OFF.'

Wire To Mains
Power Supply

5.3

 

MAINS CONNECTION

Terminate the mains connection using suitable earthed mains cable to a fused supply, ensuring all 
power is isolated before attempting to terminate and wires. This supply should not be shared with 
any other appliances.

5.2

 PRE-INSTALLATION TESTING

It is STRONGLY recommended that the panel is powered up and tested prior to the external 
system circuits being connected.

 

• 

Make sure the external system wiring has been tested and the results recorded.

 

• 

Connect the batteries together (see 

FIG 5.4, 

page 10) and connect the + & - 'spade terminals'  

   to the PCB terminal block.  Ignore the fault indication at this stage.

• 

Connect the mains supply (see 

FIG 5.3,

 page 9).  The fault indication will be removed

• 

In turn, temporally disconnect each of the monitoring resistors from the terminals, check for 

   a fault indication, and reconnect for the fault to reset.

• 

In turn, use a 470 ohm resistor to temporally connect across the detector circuit terminals 

   to create a FIRE condition.  Reset as per the Operating Instructions.
Once the panel has been tested and the operating procedure is understood, the external 
connections can be made, ONE CIRCUIT AT A TIME.

Page 9

VI40.1 Created 05/11/2001  Issue 1.3

Reviews: