46
HEI240 Wood Insert Fireplace Installation and Operation Manual
Appendix 4: Heat Shield for Surround / Shelf Installation
To install this heat shield, the purchase of the accessory AC01317 is required.
When a heat shield is installed, you can reduce the clearances to the mantle shelf and the
top surround as followed (refer to
Section 8.3
Compliance of a Combustible Mantel
Shelf
for additional details).
MAXIMUM MANTEL
SHELF DIMENSION (X)
MANTEL SHELF
CLEARANCES (I)
TOP SURROUND
CLEARANCES (H)
12" / 305 mm
21" (533 mm)
21" (533 mm)
Install the heat shield on the faceplate
(assembled with the faceplate
extension) using 3 self-drilling screws
included in the kit. The heat shield
should be pointing upwards.
Once the heat shield is positioned,
install the faceplate on the insert
following
Appendix 3:
Faceplate
Installation
.