Installation and Operation Manual - HES 240
ENGLISH
8.3.1 Shield Construction Rules
− Adhesives used in shield construction must not ignite or lose its adhesive qualities at temperatures
likely to be encountered.
− Mounting hardware which extends from the shield surface into combustibles may be used only at
the edges of the shield.
− Mounting hardware must allow full vertical ventilation.
See figures on next page for shield construction to match each letter to a clearance.
A) Minimum clearance between the appliance top and an unshielded combustible ceiling: (49
¾
")
(1245 mm)
.
B) Shield extension above the appliance: 20" (500 mm).
C) Minimum space behind the shield: 1" (25 mm). In Canada
⅞
" (21 mm).
D) Clearance along the bottom of the shield: minimum 1" (25 mm) and maximum 3" (75 mm).
E) Minimum clearance along the top of the shield at the ceiling: 3" (75 mm).
F) Mounting hardware must not be located closer than 8" (200 mm) from the vertical centre line of
the appliance.
G) Edge clearance for ceiling shields to side and back walls: 3" (75 mm).
H) Shield extension beyond each side of the appliance: 18" (450 mm).