17
FAULT HANDLING
Problem
Possible reasons
Fault handling
Fan(s) do(es)
not start
No power supply.
Make sure that the unit is properly
connected to the power mains and make
any corrections, if necessary.
Supply air too
cold
Exhaust fi lter clogging.
Clean or replace the extract fi lter.
Heat exchanger icing.
Check the heat exchanger for ice. If the
heat exchanger has iced wait till the ice
melts before re-activating the unit.
Low air fl ow
Contaminated fi lters, fans or heat
exchanger.
Clean or replace the fi lters; clean the fans
and the heat exchanger.
Ventilation system contaminated
or damaged.
Check the diff users and louvres for free
opening, check the air exhaust hood and
the supply grille - clean if necessary. Make
sure that the air ducts are not soiled and
damaged.
Noise, vibration
Contaminated fan impellers.
Clean the fan impellers.
Fan mounting screws loose.
Check the mounting screws for any
looseness.
Water leakage
Drain line clogged, damaged or
improperly arranged.
If necessary, clean the drain line. Check
the drain line slope angle and the
hydraulic back-pressure valve. Make sure
that the drain line has thermal insulation
to prevent freezing.
Possible malfunctions and their elimination