MOUNTING AND START-UP
UNIT MOUNTING
The unit is designed for suspended mounting by means of the threaded rod fixed in the threaded dowel pin.
washer
wut
vibration-absorbing
rubber
nut and
lock-nut
Example
MINIMUM ACCESS TO THE UNIT
While mounting the unit provide enough space for its servicing and maintenance.
To attain the best performance of the unit and to minimise turbulence-induced air pressure losses while mounting connect a straight
air duct section on both sides of the unit.
Minimum straight air duct length:
• equal to 1 air duct diameter on intake side.
• equal to 3 air duct diameters on outlet side.
If the air ducts are not connected or the connected air ducts are too short, protect the unit parts from ingress of foreign objects
by covering the spigots with a protecting grille or other protecting device with mesh width not more than 12.5 mm to prevent
uncontrollable access to the fans.
MINIMUM REQUIRED ACCESS TO THE UNIT
UNIT CONTROLS LOCATION
Modell
VUT 350 PE ЕС
VUT 600 PE ЕС
VUT 1000 PE ЕС
min А, mm
500
850
800
min A depends on the filter
VUT 350 PE EC - 441 mm;
VUT 600 PE EC - 784 mm;
VUT 1000 PE EC - 650 mm
(less than VUT 600 PE EC).