9
OUTDOOR TEMPERATURE SENSOR INSTALLATION
Mounting of the outdoor temperature sensor:
1. Remove two screws from the sensor cover.
2. Take off the cover from the sensor.
3. Install the sensor on the outside wall. The wall must not be
exposed to direct sunlight.
4. Install the sensor cover back.
1
3
2
4
CONNECTION TO POWER MAINS
DISCONNECT THE UNIT FROM POWER MAINS PRIOR TO ANY ELECTRIC INSTALLATION
OPERATIONS.
CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED BY A QUALIFIED ELECTRICIAN
WITH A WORK PERMIT FOR THE ELECTRIC UNITS UP TO 1000 V AFTER DETAILED STUDY OF THE
PRESENT USER’S MANUAL.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE SHOWN ON THE RATING PLATE. ANY
INTERNAL CONNECTION MODIFICATIONS ARE NOT ALLOWED AND RESULT IN WARRANTY LOSS.
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Out Gnd E+
Out Gnd E+
A
TE1
t°C
Gnd +12V
A
B
P1
1
2
PK1
Cooler
Po
w
er supply
400 V
AC
— ELECTRIC SHOCK HAZARD!
B Gnd +12V no c no c
L
N
L
N PE N L3 L2 L1
2
1
SM2
2
1
L
N
L
N
SM1
The unit is rated for connection to three-phase ac 400 V / 50 Hz. The unit shall be connected to power supply by means of insulated, durable
and thermal-resistant cords (cables, wires) with respective cross section, in any case no less than 4 mm2. The above cross section is for reference
only. The applicable cable must be selected in consideration of the maximum wire temperature depending on the wire and insulation type, the
maximum current, the lead wire length and its installation method.»
Use copper wires only.
Connect the unit to power mains through the terminal block which is located in the terminal box on the side of the unit, in compliance with
the wiring diagram and the terminal marking. Connect all the control and supply cables in compliance with the terminal marking and polarity!
Connect the unit to power mains through an external thermal-magnetic circuit breaker integrated into the fixed wiring system. The trip
current should be not below the current consumption.
Name
Наименование
Type
Wire
Cooler
DX cooler
NO
2 х 0,75 mm
2
SM1
Supply air damper actuator
LF230 2 х 0,75 mm
2
SM2
Extract air damper actuator
LF230 2 х 0,75 mm
2
PK1
Contact from fire alarm panel
NO
2 х 0,75 mm
2
P1**
Remote control
4 х 0,75 mm
2
TE1
Outdoor temperature sensor
3 х 0,75 mm
2
1. The unit delivery set includes P1 and TE1 only.
2. ** Maximum connecting cable length is 20 m!