DISCONNECT THE UNIT FROM POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED BY A QUALIFIED ELECTRICIAN WITH A
WORK PERMIT FOR THE ELECTRIC UNITS UP TO 1000 V AFTER CAREFUL READING OF THE PRESENT USER’S
MANUAL.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL.
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY.
CONNECTION TO POWER MAINS
1
X1
VUT R 400-2000 WH EC wiring diagram
X2
gnd
2
R+
3
R-
4
G
5
G0
P1 th-Tune
24V
~
GND
~
Rx+/
Tx+
Rx
-/T
x-
GND
green
Preheating enable signal (no-contact, 16 A)
Cooler enable signal (no-contact, 16 A)
Power input 230
V
AC
yellow
brown
grey
white
6
NO
7
NO
8
NO
9
NO
10
2
11
1
1
2
PK1*
12
L
13
N
14
Y
15
G
16
GO
17
PE
18
N
19
L1
1
PE
2
N
3
L
1
2
N
L
SM1*
1
2
~
Y
SM3*
1
1
2
N
L
SM2*
N
PE
M3*
L
The air-handling unit is rated for connection to single-phase AC 230 V / 50/60 Hz power mains. The connection must be made using
durable, insulated and heat-resistant cables with a minimum cross-section of 1.5 mm
2
(up to 50 m long). The cable cross-section is given for
reference only. The actual conductor cross-section selection must be based on its type, the maximum permissible heating, insulation, length
and installation method.
Use copper cables only.
Connect the unit to power mains on the terminal block which is located in the control unit in compliance with the wiring diagram and the
terminal marking.
Connect the unit to power mains through the external automatic circuit breaker with a magnetic trip integrated into the fixed wiring
system. The trip current of the automatic circuit breaker must correspond to the current consumption (see the table on page 6).
Design.
Name
Model
Wire**
M3*
Circulation pump
max 0.3 kW
3x0,75 mm
2
SM1*
Supply air damper electric actuator
TF230
2x0,75 mm
2
SM2*
Exhaust air damper electric actuator
TF230
2x0,75 mm
2
SM3*
Heat medium regulating valve actuator
LR24-SR
3x0,75 mm
2
PK1*
Contact from fire alarm panel
NC
2x0,75 mm
2
P1
Control panel
th-Tune
* - Devices are not included into delivery set, but can be delivered according to the order.
** - Wire cross-section at a cable length of maximum 100 m.
Maximum cable length from controller to control panel
Cable type
Distance to power source
Phone cable
up to 50 m
AWG24 shielded cable
up to 200 m
—
Electric shock hazard!