INSTALLATION AND SET-UP
READ THE USER’S MANUAL PRIOR TO MOUNTING THE UNIT.
THE UNIT MUST BE MOUNTED BY A QUALIFIED EXPERT ONLY, PROPERLY TRAINED AND
HAVING THE REQUIRED TOOLS AND MATERIALS.
While mounting the unit provide enough access for maintenance or repair work.
The minimum recommended clearances between the unit and the adjoining walls are given in the figure below.
Before starting the unit make sure that the rotary heat exchanger cells are clean and free from damage.
Check the belt tension. The tension force is regulated by the spring on the motor suspension mount.
The unit may be suspended on a threaded rod that is fixed inside a dowel or may be rigidly fixed on a horizontal or vertical plane.
SUSPENDED MOUNTING OF THE UNIT
Screw
Vibration absorbing
rubber
Expansion anchor
min 400 mm
min 400 mm
Nut
Threaded rod
Washer
Vibration absorbing
rubber
Washer
Nut and lock nut
UNIT WALL MOUNTING
Screw
Vibration absorbing
rubber
Expansion anchor
min 400 mm
To get the best performance of the unit and to minimize turbulence-induced air pressure losses, connect the straight air duct section to
the spigots on both sides of the unit while installing.
Minimum straight air duct length:
• equal to 1 air duct diameter on the intake side
• equal to 3 air duct diameters on outlet side
If the air ducts are too short or not connected, protect the unit parts from ingress of foreign objects.
To prevent uncontrollable access to the fan, the spigots may be covered with a protecting grille or other protecting device with mesh