background image

2.2.b .   Functions of the programming module: (1)

Adjustment using the clock:
Navigate with keys 19 or 20 to pictogram 1 showing a clock. 
Select with key 18 The pictogram will flash Validate with key 18

Select with key 18. The pictogram will flash. Validate with key 18.
Adjust the desired hour using keys 19 and 20. 
Validate with key 18. Pictogram 3 (day) will flash. Validate with key 18.
Adjust the day, knowing that the succession can be destined from 1 to 7 on any day.

Airflow adjustment (From 90 m

3

/h to 275 m

3

/h): (5)

Minimum airflow:
Navigate with keys 19 or 20 to pictogram 4 showing flows. 
Select with key 18. The pictogram of the first fan will flash. Validate with key 18.
Adjust the minimum desired flow using keys 19 and 20 in 5 m

3

/h steps, according to the 

configuration of your house (in compliance with the table). 

Maximum airflow:
Validate with key 18 The pictogram with two fans will flash Validate with key 18

Validate with key  18. The pictogram with two fans will flash. Validate with key 18.
Adjust the maximum desired flow using keys 19 and 20 in 5 m

3

/h steps, according to the 

configuration of your house (following the table show below).

Validate with key 18.

Programming module options (2):
There are two pre-established programming modes and one user-chosen mode. The 
modes are to past to the minimum airflow at the maximum airFlow.
To access the desired mode:
Navigate with keys 19 or 20 to Auto 1, Auto 2  or Manu pictogram . (Automatic 1, Automatic 
2 or Manual)
Select with key 18. Select On/Off using keys 19 or 20. Validate the chosen programming 
with key 18.

- Auto 1:
Working week with two meals per day, three in the weekend, but starting breakfast two 
hours later.

Day

Start

Finish

Start

Finish

Start

Finish

Monday

6:30

7:30

19:30

20:30

T1

T2

T3

Monday

6:30

7:30

-

-

19:30

20:30

Tuesday

6:30

7:30

-

-

19:30

20:30

Wednesday

6:30

7:30

-

-

19:30

20:30

Thursday

6:30

7:30

-

-

19:30

20:30

Friday

6:30

7:30

-

-

19:30

20:30

Saturday

8:30

9:30

12:00

13:00

19:30

20:30

Sunday

8:30

9:30

12:00

13:00

19:30

20:30

Summary of Contents for IDEO - 275 Ecowatt

Page 1: ...CTB IDEO 275 Ecowatt Installation Manual...

Page 2: ...Before manipulating this device disconnect the electricity supply During normal operation never stop the ventilation system...

Page 3: ...homes Soler Palau will not be held liable for damage produced by Misuse Normal wear and tear of components Non observance of the instructions contained in this manual regarding safety use and start up...

Page 4: ...ed airflows are separated and filtered Only the energy from the extracted air is transferred to the new fresh air introduced Thanks to IDEO 275 Ecowatt s high efficiency heat exchanger performance can...

Page 5: ...avoid thermal losses and optimise the performance of the installation it is d d t i l t d t b f i th i recommended to use insulated tubes for moving the warm air Discharge extracted air to outside Th...

Page 6: ...2 3 Dimensions Central unit Weight 51 Kg Remote controls Programmable module Kitchen boost...

Page 7: ...Wall bracket 2 4 Placement On a vertical wall On the floor It is recommended to locate IDEO in heated house space Otherwise it will be necessary to insulate the condensate drain pipework...

Page 8: ...fic kit option Support It is recommended to locate IDEO in heated house space Otherwise it will be necessary to insulate the condensate drain pipework necessary to insulate the condensate drain pipewo...

Page 9: ...Y Kitchen Outlet roof caps CT 150 Toilets BDOP 125 BDOP 80 Toilets Air intake plenum PAP Air intake D150 Li i itti Or PAF 150 Circular Air intake wall hoods Living sitting room Bedrooms Or Or PAST Air...

Page 10: ...TYPE DISTRIBUTION Outlet roof caps CT 150 Living sitting room BDOP 125 Kitchen BDOP 125 BDOP D80 RD80 Bedrooms Toilets BAR Toilets PAP Air intake D150mm BDOP D80 RD80 Or PAF 150 Circular Air intake D...

Page 11: ...aracteristics of each installation If any component is missing or badly fitted normal operation may be impaired H05VV F 5G1 type cable Length 1 2 m Connection box Electrical panel Power supply Single...

Page 12: ...type battery The programming module is located on the front of the machine This remote control can also be located on a wall The programming module is located on the front of the machine This remote c...

Page 13: ...or large flow 6 By pass 7 Defrost mode 7 Defrost mode 8 Absence mode 9 Transmission reception level 10 Battery level 11 Default mode 12 Change filter 12 Change filter 13 Instant energy saving 14 Energ...

Page 14: ...alidate with key 18 Validate with key 18 The pictogram with two fans will flash Validate with key 18 Adjust the maximum desired flow using keys 19 and 20 in 5 m3 h steps according to the configuration...

Page 15: ...ass Select with key 18 Select ON using keys 19 or 20 Validate with key 18 You can disable the forced by pass mode at any time To do this Navigate with keys 19 or 20 to pictogram 6 showing the By pass...

Page 16: ...played 11 This icon is displayed when one of the components is out of service motor probe This icon is displayed when one of the components is out of service motor probe sensor Or if the IDEO detects...

Reviews: