5.2 Review and maintenance
The set between routine checks and maintenance should be determined by user, based on the observation of unit and specific conditions of
use, in order to include specific work conditions. The set cannot be longer than introduced below
In the case of irregularities the device must be turn off and subjected to review, maintenance and possible repairs / cleaning (when dirt
occurs). Examples of reasons for device to work in emergency mode are given in Appendix D.
People operating the device must be familiar with it normal working conditions. If the fan work differ from it normal working conditions it
need to be turn off from work, inspected and repaired / cleaned.
Recommended daily review, not less frequently than once a week.:
Device is undamaged, stable and works properly
There are not any leaks, smoke from motor
Device does not emit any untypical noise, and does not heat up excessively
Device is clean (external control), corrosion does not occur (external control)
Wires are not damaged
There are no unusual leaks (unit is properly sealed)
Covers are in proper state and clean
Recommended monthly review, not less frequently than once a 3 months.:
Fan current value is not higher than beginning value
The values of generated vibration did not increase (according to beginning value)
Device and covers are clean
Device is clean, filter (if applied) is not clogged.
There are no foreign elements, and loose parts inside fan.
Review once per 3 months, not less than 6 month and 3000 hours of work
Corrosion does not occur (detailed control)
Fasteners state is proper (they are properly tightened)
Security devices are working and set properly, protection against electrical shock is effective.
Motor insulation resistance value is correct
Impeller is able to freely rotate, bearings are not loose and rotation of impeller does not make too much noise.
Structure is not damaged, components are not damaged (
e.g. by abrasion
)
Minimum in ten years time the impeller need to be controlled due to fatigue strength. At leas once per month drain excess of condensate
through a condensation value.
6. REPAIR, WARRANTY
Use only original spare parts and original accessories. Fan repairs need to be made by Venture Industries Sp. z o.o. service or outside, after
manufacturer permission. Warrantee conditions are described in guarantee card.
7. DISMANTLING AND RECYCLING
Disconnect unit from its power supply, and dismount according to the guidelines from section 1 of this instruction. Therefore, please deposit all
left-over material and packaging in their corresponding recycling containers and hand in the replaced machines to the nearest handler of this
type of waste product.