I-Ga te 4000 P R O Ins tall ation
Cabinet Instal lation
02041802-05
Veraz Networks Inc. Proprietary
5-7
3. Insert expansion shields into holes.
4. Slightly loosen the screw (M8) that connects the upper bracket to the wall
bracket. This allows you to adjust the precise location of the cabinet with respect
to the wall. The maximum distance from the wall should be 100 mm.
5. Using the wood screw, secure the upper bracket to the wall.
6. Once the cabinet and the upper bracket are exactly where you want them, tighten
the screw (M8) that connects them.
SCREW M8X30
FLAT WASHER
LOCK WASHER
NUT M8
UPPER BRACKET
WALL
WALL BRACKET
75.0
WOOD SCREW 8X70
ANCHOR 10X50
0-100.0
0-100.0 max
Figure
5-5: Connecting the ETSI cabinet to a wall