I-Ga te 4000 P R O Ins tall ation
Cabinet Instal lation
02041802-05
Veraz Networks Inc. Proprietary
5-13
16. Connect the grounding cable, to the underside of the 19in./47U high cabinet,
using the appropriate screws.
17. Complete the leveling and tightening of the remaining 19in./47U high cabinets,
as described above. Ensure that the cabinets are flush with one another.
FLOATING FLOOR LEVEL
Figure
5-9: Bolting the
19in./47U
high cabinet to a floating floor
5.2.3. Mounting the 19in./47U high Cabinets Rack-to-
Rack
The procedure below describes mounting the 19in./47U high cabinets rack-to-rack.
To mount the19in./47U cabinets rack-to-rack:
1. Remove the side walls between the racks (see Figure 5-10). These are normally
used for single rack installation.
2. For Rack-to-Rack mounting, rotate triangles (see callouts 1 and 2 in Figure 5-
10). Use M10x25 screws with corresponding nuts and washers.
3. Mount racks in the same way as described in Sections 5.2.1 and 5.2.2.