25
05 – INCIDENTAL OCCUPANCY THRESHOLD
00-60
(05* default setting) Select the minimum period of time (in
minutes) for which occupancy needs to be detected to enter
the guest occupancy mode.
When occupancy is detected, thermostat will switch to
occupied mode for a duration of “Incidental Occupancy
Threshold” selected here.
If occupancy is detected for a period of time shorter than the
“Incidental Occupancy Threshold” selected here, the thermostat
will automatically revert to unoccupied mode at the end of
the “Incidental Occupancy Threshold” period and continue to
observe energy saving functions that were in effect before the
room became occupied. This setting allows ignoring incidental
room visits.
If occupancy is detected for a period of time longer than the
“Incidental Occupancy Threshold” selected here, the thermostat
will enter the guest occupancy mode. When the thermostat
is in the guest occupancy mode, it will revert to unoccupied
mode and initiate the setback temperature only when
occupancy is not detected for the duration of the setback delay
(Heat or Cool) period.
Custom Energy Savings Settings