10 – TEMPERATURE RECOVERY TIME
00-60
(25* default setting) Select the maximum time allowed for a
PTAC unit to attain temperature as defined by Heat and Cool
“Recovery Temperature”.
“Temperature Recovery Time” selected here and the actual
temperature recovery ability of the PTAC unit are used
to calculate setback temperatures. Calculated setback
temperatures maximize energy savings and at the same time
ensure that a comfortable room temperature (defined as Heat
and Cool “Recovery Temperature”) will be restored within the
selected “Temperature Recovery Time”.
Setting the “Temperature Recovery Time” to “00”, disables
temperature recovery. When temperature recovery is disabled,
thermostat will use the Minimum and Maximum Setback
Temperatures as setback set points.
Custom Energy Savings Settings