40
20 – AUTO CHANGEOVER SET POINT OFFSET (DEAD BAND)
00-04
(01°F* default setting) Select the difference between the guest-
selected set point and the heat and the cool set point when
the thermostat is in the automatic temperature control mode.
This value plus the 1st stage differential defined in steps 02 and
04, defines the temperature at which the thermostat would
automatically change heating/cooling modes.
This feature allows adjusting the dead band between the heat
and the cool set points in automatic changeover mode in order
to avoid the system from bouncing back and forth between
heating and cooling under normal operating conditions.
.
Custom Energy Savings Settings