10.0
Fuses and Power Settings
10.1
Fuses
F1-F3: Refer to the circuit diagrams.
F1
Internal
Supply
Fuses
Fitted if supply cable fitted.
Fitted on board to some types
of EMC filter.
GEC Safeclip of the type shown
(glass type F up to 16 A)
38 mm x 10 mm type F fitted on
EMC filter circuit board(s)
F2
Auxiliary
Circuit Fuses
Fitted on board to some types
of EMC filter.
May be omitted up to 25 Amp/
phase supply rating.
2 Amps glass type F
On board: 20 mm x 5 mm
Other: 32 mm x 6 mm
F3
Heat Light
Fuses
May be omitted up to 25 Amp/
phase supply rating.
2 Amps glass type F
32 mm x 6 mm
Customer
Fuses
Required if no supply cable
fitted.
Recommended if cable fitted.
See rating label for current;
See table below for fuse rating.
Model
Phases
Volts
Supply Fuse Rating
CFM 14/1 + Aux
1-phase
220-240
16 A
10.2
Power Settings
The power limit settings (parameter OP.Hi) for this model are voltage dependant. The
figures represent the maximum percentage of time that controlled power is supplied to
the elements. Do not attempt to “improve performance” by setting a value higher than
the recommended values. To adjust the parameter refer to the "Changing the
Maximum Output Power" of the control section of the manual.
Volts
110 V
120 V
220 V
230 V
240 V
Volts
220 V
230 V
240 V
Power (%)
55
100
92
Auxiliary heater models: the power limits for the controllers for the auxiliary
heaters have power limits of 100%.
39
10.0 Fuses and Power Settings
Summary of Contents for CARBOLITE CFM 14/1 AUX
Page 4: ...User Power Setting Adjustments 40 11 0 Specifications 41 11 1 Environment 41 4 ...
Page 6: ...1 0 Symbols and Warnings Caution Double Pole Neutral Fusing 6 ...
Page 20: ...3 0 2416 Controller 3 6 Navigation Diagram 20 ...
Page 37: ...9 0 Wiring Diagrams 9 1 WB 12 10 AUX 9 2 WB 12 11 AUX 37 9 0 Wiring Diagrams ...
Page 38: ...9 0 Wiring Diagrams 38 ...
Page 42: ......
Page 43: ...Notes Service Record Engineer Name Date Record of Work ...