4.0 2416 Controller
For a more detailed view, press page
to access the 'Run' list page and scroll
to see
its contents as shown in the Navigation Diagram below. Provided the unit is first put into
'Hold' mode, temporary changes may be made to parameters; these apply only until
the program ends or is reset.
To pause a program, press Run/ Hold; the 'Hold' light comes on. To terminate a
program, press Run/ Hold for 2 seconds; the 'Run' and 'Hold' lights go out.
While the program is operating, the working setpoint is shown in the lower display.
4.3.6
Program example
The following sequence of entries creates and runs the program.
1. Press page
key until 'ProG LiSt' is displayed.
2. Press scroll
until 'CYC.n' is displayed and use the arrow key to select 1.
3. Press scroll
until 'SEG.n' is displayed and use the arrow key to select 1.
4. Press scroll
until 'tYPE' is displayed and use the arrow key to select rmP.r.
5. Press scroll
until 'tGt' is displayed and use the arrow key to select 600.
6. Press scroll
until 'rAtE' is displayed and use the arrow key to select 5.0.
7. Press scroll
until 'SEG.n' is displayed and use the arrow key to select 2.
8. Press scroll
until 'tYPE' is displayed and use the arrow key to select dwEl.
9. Press scroll
until 'dur' is displayed and use the arrow key to select 60.0.
10. Press scroll
until 'SEG.n' is displayed and use the arrow key to select 3.
11. Press scroll
until 'tYPE' is displayed and use the arrow key to select rmP.t.
12. Press scroll
until 'tGt' is displayed and use the arrow key to select 400.
13. Press scroll
until 'dur' is displayed and use the arrow key to select 60.0.
14. Press scroll
until 'SEG.n' is displayed and use the arrow key to select 4.
15. Press scroll
until 'tYPE' is displayed and use the arrow key to select 'dwEll'.
16. Press scroll
until 'dur' is displayed and use the arrow key to select 30.
17. Press scroll
until 'SEG.n' is displayed and use the arrow key to select 5.
18. Press scroll
until 'tYPE' is displayed and use the arrow key to select rmP.r.
19. Press scroll
until 'tGt' is displayed and use the arrow key to select 30.
20. Press scroll
until 'rAtE' is displayed and use the arrow key to select 5.0.
21. Press scroll
until 'SEG.n' is displayed and use the arrow key to select 6.
22. Press scroll
until 'tYPE' is displayed and use the arrow key to select 'End'.
23. Press scroll
until 'End.t' is displayed and use the arrow key to select 'dwEll'.
24. Press the page
key until you return to the main display.
25. Press the 'Run' key. The program operates.
18
Summary of Contents for CARBOLITE GERO ABF 8/28
Page 11: ...Fig 14 Schematic for Mains Electrical Connections 11 3 0 Installation ...
Page 21: ...4 6 Navigation Diagram 21 4 0 2416 Controller ...
Page 33: ...5 7 Navigation Diagram 33 5 0 Afterburner 2132 Controller ...
Page 40: ...7 0 Operation Photo 3 5 40 ...
Page 53: ...Notes Service Record Engineer Name Date Record of Work ...