If not all the segments are used for a program, the Ramp & Dwell of each of the
subsequent segments should be set to OFF.
A program will end in one of two ways, either revert to the control setpoint or dwell at
the temperature set in the last segment used. When a program finishes on a dwell and
the dwell time expires the temperature will revert to the control setpoint.
Note: Before operating a program ensure that the control setpoint is set to Zero to
avoid unexpected heating at the end of the program.
4.7.9
Running a Program
If using the 3216P5 controller press scroll
to display PROG <PROGRAM NUMBER>.
Select the required Program Number before operating a Program.
Table below shows the key presses to operate a program.
Operation
Action
Indication
To RUN a program
Press and quickly release
+
Indicator – RUN = ON
Scrolling Display – Current
Program state
To HOLD a program
Press and quickly release
+
Indicator – RUN = Flashing
Scrolling Display – Program Hold
To RESET a program Press and hold
+
for
more than 1 second
Indicator – RUN = OFF
Scrolling Display - None
Program Ended
Indicator – RUN = OFF
Scrolling Text – Program End
To RESET a
program after it has
completed
Press and hold
+
for
more than 1 second or press
and quickly release Ack
Indicator – RUN = OFF
Scrolling Display - None
4.7.10
Program Status
While the program is operating in level 1 or level 2, the home display shows two values
at any one time:
4.7.11
Process Value
The upper display shows the current temperature of the product.
4.7.12
PSP, Segment Type and Number
The lower display continually alternates between the programs current set value
(Program SP = PSP) and scrolling text, indicating the current status of the program
whether RAMP or DWELLING followed by the segment number.
Additional information can be obtained using the scroll
key while the program is
operating.
21