TM
CURRENT MONITORING
INSTALLATION GUIDE
Solid-Core Current Switch, Adjustable Trip Point
Installer’s Specifications
Sensor Power
Induced from the monitored conductor
Amperage Range
0.75 to 50 A continuous*
Insulation Class
600 VAC RMS (UL)
Frequency Range
50/60 Hz
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range
10-90% RH non-condensing
Hysteresis
10% typical
Status Output
N.O. 0.2 A@120 VAC, polarity sensitive
Off-State Resistance
1 MΩ
On-State Resistance 20
Ω
Terminal Block Max. Wire Size
14 AWG
Terminal Block Torque (nom.)
4 in-lbs (0.45 N-m)
Agency Approvals
UL508 E150462
The product design provides for basic insulation only.
* When operating at 50 Hz, low threshold may be 0.9 A.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
WIRING EXAMPLE
H809
TM
809
DIMENSIONS
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
INSTALLATION
Disconnect and lock out power to the enclosure containing the
conductor to be monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow
the monitored conductor to pass through the center window when it is installed
and that will keep the device at least 1/2” from any uninsulated conductors.
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.
2. Drill holes to mount the bracket to the chosen surface using the included screws.
3. Wire the output connections and relay between the sensor and the controller
(solid-state contact).
4. Route the conductor through the sensor’s center window and slip the assembly
into the mounting bracket.
5. Secure enclosure and reconnect power.
6. Calibrate sensor with load running normally.
0 0.7"
(18 mm)
0.4” x 0.2”
Slot (x2)
2.8"
(71 mm)
1.7
(43 mm)
2.3"
(58 mm)
1.1"
(27 mm)
0.9"
(23 mm)
Removable/Adjustable Mounting Bracket
Motor
Fan or Pump
DDC CONTROLLER
DI
-
+
CONTACTOR
www.
GlobalTestSupply
.com
Find Quality Products Online at:
sales@GlobalTestSupply.com