Installation Guide
Temperature
TWS Series
TM
Dimensions
1.2"
(29 mm)
3.5"
(89 mm)
4.75"
(121 mm)
-
+
Installation
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Locate the tab at the top of the sensor housing. Using only the minimum required force, press this tab down and pull the cover
outward from the top. Set the cover aside.
Housing, Top View
Tab
2. Remove the backplate by unfastening the sensor from the bottom of the backplate and pivoting the sensor outward.
3. Punch out wire opening in the backplate.
4. Position the backplate vertically on the wall, 4 ½ feet (1.4 m) above the floor. Locate away from windows, vents, and other
sources of draft. If possible, do not mount on an external wall, as this might cause inaccurate temperature readings.