background image

Z203399-0C 

PAGE 1 

©2012 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / support@veris.com  

02122

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

TM

RELAYS

INSTALLATION GUIDE

Dual 10A SPDT Enclosed Relays

10-30 VDC/AC or 120 VAC Coil

Installer’s Specifications

Operating Temperature -40°C to 55°C (-40° to 131°F)

Operating Humidity 

10-90% non condensing

Expected Relay Life 

Electrical (at rated current):  100,000 cycles

 Mechanical 

(unpowered):  10,000,000 cycles

Relay Status 

LED ON=energized

Wire Specifications:

   Lead Length 

14” (356mm) min.

   Gauge 

UL1015; Coil:  18 AWG; Contacts:  16 AWG

Insulation Class 

600 VAC RMS

Agency Approvals 

UL508 enclosed device listing

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

•  Follow safe electrical work practices. 

See NFPA 70E in the USA, or applicable local codes.

•  This equipment must only be installed and serviced by qualified electrical personnel.
•  Read, understand and follow the instructions before installing this product.
•  Turn off all power supplying equipment before working on or inside the equipment.
•  Use a properly rated voltage sensing device to confirm power is off.
  DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION

Failure to follow these instructions will result in death or serious injury.

DANGER 

V100D

V100D

DIMENSIONS

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  The installer is responsible for conformance to all applicable codes.

•  Mount this product inside a suitable fire and electrical enclosure.

INSTALLATION

Disconnect and lock out all power sources before beginning the 

installation.

1.  Using the threaded nipple connect the relay to the desired enclosure through a 

knock out hole.

2.  Secure with the conduit nut provided.

Relay #1

3.  Connect Coil:

• 

 Choose the coil common lead (white with yellow stripe) and connect it to 
the (-) source termination point.

• 

 Choose either the low voltage (10-30VAC/DC, white with blue stripe) or 
high voltage (120VAC, white with black stripe) lead, depending on the 
application requirements, and connect it to the (+) source termination 
point.*

NOTE:  When connecting the control side of this device (#18 wires) to power 
line circuits, provide current limiting at 7 amps max.

4.  Connect Relay Contacts:

• 

Choose the relay common wire (yellow) and connect to switched load.

Relay #2

5.  Connect Coil:

• 

 Choose the coil common lead (white with violet stripe) and connect it to 
the (-) source termination point.

• 

 Choose either the low voltage (10-30VAC/DC, grey with white stripe) 
or high voltage (120VAC, white with red stripe) lead, depending on the 
application requirements, and connect it to the (+) source termination 
point.*

NOTE:  When connecting the control side of this device (#18 wires) to power 
line circuits, provide current limiting at 7 amps max.

6.  Connect Relay Contacts:

• 

 Choose the relay common wire (violet) and connect to switched load.

• 

 Choose the relay N.O. (brown) and/or* N.C. (grey) lead and connect to  
switched load.

7.  Secure the enclosure and reconnect power.

* Isolate or insulate all non-terminated wires according to local electrical code requirements, i.e. 
wire nut.

2.0"

(52 mm)

2.5"

(64 mm)

3/4" NPT Nipple

2.3"

(59 mm)

4.0"

(103 mm)

3.8"

(97 mm)

Reviews: