Preinstallation
requirements
This chapter includes the following topics:
■
Customer-provided environment and supplies
■
Appliance shipping container contents
■
Electrical and environmental requirements
■
■
Prerequisites for the Veritas Remote Management Interface configuration
Customer-provided environment and supplies
For best ventilation, the rack cabinet:
■
Should be at least 100 cm (4 feet) from walls.
■
Should have at least 100 cm (4 feet) from other cabinets on the front and back
of the appliance.
Data centers with two-foot spaces in the front and in the back of the appliances are
acceptable with proper cooling and ventilation.
Refer to the following section for more details.
See
on page 18.
The following describes the necessary personnel and equipment that are needed
at the installation site:
■
At least one person or a mechanical lift to move the appliance.