20306757
17
CSDV Series Direct Vent Gas Stove
HOT
H
V
ST1139
Horizontal termination
VENTING INSTALLATION
Figure 18 -
Horizontal Termination Configuration for Rigid Venting
Using One (1) 90° Elbow
NOTE:
Add 1/4" rise per 12" horizontal length of pipe.
NOTE:
This configuration is for use with corner
installation also.
H
1
H
V
ST1140
Horiz term 2 elbows
Figure 19 -
Horizontal Termination Configuration for Rigid Venting
Using Two (2) 90° Elbows
NOTE:
Add 1/4" rise per 12" horizontal length of pipe.
Table 2: Horizontal Venting
Maximum Horizontal (H)
Minimum Vertical (V)
24" (610 mm)
52
1
⁄
2
" (1334 mm)
20' (6 m)
98
1
⁄
4
" (2495 mm)
Table 3: Horizontal Venting with Two (2) 90°
Elbows
Maximum Horizontal
(H+H
1
)
Minimum Vertical (V)
24" (610 mm)
52
1
⁄
2
" (1334 mm)
20' (6 m)
98
1
⁄
4
" (2495 mm)
INSTALLATION FOR VERTICAL TERMINA
-
TION
1. Determine the route your vertical venting will take.
If ceiling joist, roof rafters or other framing will
obstruct the venting system, consider an offset.
Refer to Figure 22
to avoid cutting load bearing mem-
bers.
NOTE:
Pay special attention to these installation instructions
for required clearances (air space) to combustibles when
passing through ceilings, walls, roofs, enclosures, attic
rafters, etc. Do not pack air spaces with insulation. Also
note maximum vertical rise of the venting system and any
maximum horizontal offset limitations. Offsets must fall
within the parameters shown on
Page 14, Figure 11.
2. Set stove in desired location. Drop a plumb line down
from the ceiling to the position of the burner system exit
flue. Mark the center point where the vent will penetrate
the ceiling. Drill a small locating hole a this point.
Drop a plumb line from the inside of the roof to the locat-
ing hole in the ceiling. Mark the center point where the
vent will penetrate the roof. Drill a small locating hole
at this point.
FLAT CEILING INSTALLATION
1. Cut a 9
1
⁄
2
" (241 mm) square hole in the ceiling using the
locating hole as a center point The opening should be
framed to 9
1
⁄
2
" x 9
1
⁄
2
" (241 x 241 mm) inside dimensions
as shown in
Figure 24
using framing lumber the same
size as the ceiling joist. If the area above the ceiling is
an insulated ceiling or a room, nail firestop from the top
side. This prevents loose insulation from falling into the