background image

20306757

17

CSDV Series Direct Vent Gas Stove

HOT

H

V

ST1139
Horizontal termination

VENTING INSTALLATION 

Figure 18 - 

Horizontal Termination Configuration for Rigid Venting 

Using One (1) 90° Elbow

NOTE:

 Add 1/4" rise per 12" horizontal length of pipe.

NOTE:

 This configuration is for use with corner 

installation also. 

H

1

H

V

ST1140
Horiz term 2 elbows

Figure 19 - 

Horizontal Termination Configuration for Rigid Venting 

Using Two (2) 90° Elbows

NOTE:

 Add 1/4" rise per 12" horizontal length of pipe.

Table 2: Horizontal Venting

Maximum Horizontal (H)

Minimum Vertical (V)

24" (610 mm)

52

1

2

" (1334 mm)

20' (6 m)

98

1

4

" (2495 mm)

Table 3: Horizontal Venting with Two (2) 90°

 Elbows

Maximum Horizontal 

(H+H

1

)

Minimum Vertical (V)

24" (610 mm)

52

1

2

" (1334 mm)

20' (6 m)

98

1

4

" (2495 mm)

INSTALLATION FOR VERTICAL TERMINA

-

TION

1. Determine the route your vertical venting will take. 

If ceiling joist, roof rafters or other framing will 

obstruct the venting system, consider an offset. 

 

Refer to Figure 22 

to avoid cutting load bearing mem-

bers. 

NOTE:

 Pay special attention to these installation instructions 

for required clearances (air space) to combustibles when 

passing through ceilings, walls, roofs, enclosures, attic 

rafters, etc. Do not pack air spaces with insulation. Also 

note maximum vertical rise of the venting system and any 

maximum  horizontal  offset  limitations.  Offsets  must  fall 

within the parameters shown on 

Page 14, Figure 11.

2.  Set stove in desired location. Drop a plumb line down 

from the ceiling to the position of the burner system exit 

flue. Mark the center point where the vent will penetrate 

the ceiling. Drill a small locating hole a this point. 

  Drop a plumb line from the inside of the roof to the locat-

ing hole in the ceiling. Mark the center point where the 

vent will penetrate the roof. Drill a small locating hole 

at this point. 

FLAT CEILING INSTALLATION

1.  Cut a 9

1

2

" (241 mm) square hole in the ceiling using the 

locating hole as a center point The opening should be 

framed to 9

1

2

" x 9

1

2

" (241 x 241 mm) inside dimensions 

as shown in 

Figure 24

 using framing lumber the same 

size as the ceiling joist. If the area above the ceiling is 

an insulated ceiling or a room, nail firestop from the top 

side. This prevents loose insulation from falling into the 

Summary of Contents for CSDV30NVEMBCSB

Page 1: ...Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be perfor...

Page 2: ...tems Needed 22 Check Gas Pressure 23 CONGRATULATIONS You have purchased a state of the art gas appliance featuring the Lex Fire Burn System available exclusively on Vermont Castings Group The Lex Fire...

Page 3: ...alled by a qualified service person The glass door must be properly seated and sealed If this unit is not properly installed by a qualified service person with glass door properly seated and sealed co...

Page 4: ...replacement of the unit 19 Do not operate stove if any log is broken 20 Do not use a blower insert heat exchanger insert or other accessory not approved for use with this stove 21 Do not operate the...

Page 5: ...DV Cast Iron Stove Controls ON OF F FP2724 CSDV controls Pilot Optional Remote Receiver Door Hi Lo Knob On Off Switch Optional Blower Ignitor Box Located Under Right Front Leg HIGH ELEVATIONS Input ra...

Page 6: ...6 20306757 CSDV Series Direct Vent Gas Stove STOVE DIMENSIONS Figure 2 Stove Dimensions 586056 CSDV dims 261 2 673 mm 21 533 mm 281 2 724 mm...

Page 7: ...ts Locate the stove where it can be accessed by a gas supply line Locate the stove in a large and open room that is centrally located in the house This will optimize heat circulation and comfort The f...

Page 8: ...ll be installed on a metal wood or noncombustible material panel extending full width and depth of the appliance A E Minimum D Minimum to Either Side Wall ST1128 sidewall clearance Ceiling Mantel Side...

Page 9: ...F A C B ST1132 alcove clearances Figure 5 Alcove Clearances NOTE Maintain minimum side and back clearances when placing stove in alcove ALCOVE CLEARANCES ALCOVE MINIMUM DIMENSIONS Height from Hearth W...

Page 10: ...from inside of unit 7 Lift unit off pallet Lift unit up high enough to clear upright supports unit is sitting on NOTE You will need at least two 2 strong people to lift unit off of pallet UNPACKING ON...

Page 11: ...outside The venting system must NEVER be attached to a chimney serving a separate solid fuel burning appliance Each gas appliance must use a separate vent system Do not use common vent systems WARNIN...

Page 12: ...s Minimum clearance between vent pipes and combustible materials such as insulation is 1 WARNING Never run the vent pipe level or downward This may cause excessive temperatures which could cause a fir...

Page 13: ...for appliances 100 000 BTU h 30kW 6 15cm for appliances 10 000 BTU h 3kW 9 23cm for appliances 10 000 BTU h 3kW and 50 000 BTU h 15kW 12 30cm for appliances 50 000 BTU h 15kW C Clearance to permanentl...

Page 14: ...stible Noncombustible 12 305 mm M Balcony with perpendicular side wall M 12 305 mm P 6 152 mm M F Alcove Applications C D C E V V Combustible Noncombustible E Min 2 51 mm for non vinyl sidewalls Min 1...

Page 15: ...male end of adjacent pipes and fittings Push the pipe sections together and twist one section clockwise approximately one quarter turn until the sections are fully locked Figure 14 FP1953 rigid pipe...

Page 16: ...vent pipe before con necting the horizontal run to the vent cap Figure 18 6 Carefully move the stove with vent assembly attached toward the wall and insert the vent pipe into the hori zontal terminat...

Page 17: ...tention to these installation instructions for required clearances air space to combustibles when passing through ceilings walls roofs enclosures attic rafters etc Do not pack air spaces with insulati...

Page 18: ...ole must be measured on the horizontal Actual length may be larger depending on the pitch of the roof There must be a 1 minimum clearance from the vent pipe to combustible materials Frame the opening...

Page 19: ...al ceiling installations can be very tricky 1 Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box Mark the outline of the cathedral ceiling support box...

Page 20: ...gure 27 Vertical Rigid Venting Configuration using Three 3 90 Elbows with Two 2 Horizontal Runs H V V1 ST1146 vert vent 2 elbows NOTE Install restrictor into 4 collar of stove or first vent section as...

Page 21: ...Number Description 902B 65 8 x 48 Pipe 903B 65 8 x 36 Pipe 904B 65 8 x 24 Pipe 906B 65 8 x 12 Pipe 907b 65 8 x 9 Pipe 908B 65 8 x 6 Pipe 911B 65 8 Adjustable 11 145 8 Pipe 940 Wall Thimble 941 Cathed...

Page 22: ...regulator The external regulator will reduce incoming gas pressure You must reduce incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming gas pressure burner system r...

Page 23: ...t you install a sediment trap drip leg in supply line as shown in Figure 31 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system between fuel supply and burner...

Page 24: ...ational Electrical Code ANSI NFPA 70 latest edition and Canadian Electrical Code CSA C22 1 CAUTION Label all wires before disconnecting when servicing controls Wiring errors can cause improper and dan...

Page 25: ...ins against left side of firebox 5 Place right base log 3 on the two pins against right side of firebox 6 Place top left log 4 on left base log Line up the notch in the bottom of the top log with the...

Page 26: ...REN TO TOUCH GLASS A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed for the protection of children and other at risk ind...

Page 27: ...neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If t...

Page 28: ...urner connections Field made joints gas shutoff valve Pilot Factory made joints Each joint or connection All joints on valve and control body 1 Depress and turn knob counterclockwise to pilot position...

Page 29: ...on is in the ON position to light the main burner LIGHTING THE BURNER Depress and turn the knob counterclockwise to the ON position It will take less than four 4 seconds for the burner to ignite PILOT...

Page 30: ...high altitude as follows To increase air mixture pull down the adjustment rod located beneath the stove This opens the shutter more and will stop sooting Figure 37 To decrease air mixture push up the...

Page 31: ...n the door Do not use abrasive cleaners They will damage the glass surface PILOT AND BURNER FLAMES Visually check pilot and burner flames periodically Refer to Figure 42 for typical pilot flame Refer...

Page 32: ...s pane with tadpole gasket Make sure you have 1 4 overlap on each side 7 Place new glass in frame 8 Slide glass frame back down onto stove and fasten two clamps Figure 41 9 Insert front into the top o...

Page 33: ...Adjust and retighten Pilot will not stay lit 1 Defective thermocouple Loose thermocouple 2 Air in gas line 3 No gas 1 Check for proper connection of thermocouple to rear of valve 2 Bleed line Contact...

Page 34: ...9 20 21 22 17 3 4 13 12 16 5 11 2 15 1 14 6 10 8 7 9 586056 CSDV30 parts 26 WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved w...

Page 35: ...Knob 1 45D0237 45D0237 12 Knob Extension Hi Lo 1 43D0095 43D0095 13 Knob Extension ON OFF 1 43D0094 43D0094 14 Ignitor Battery Module 1 45D0077 45D0077 15 Ignitor Wire Harness 1 45D0500 45D0500 16 ON...

Page 36: ...ys to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed MASSACHUSETTS RESIDENTS ONL...

Page 37: ...tion damage damage from unauthorized service incidental or consequential damage or negative pressure caused by mechanical systems such as furnaces fans clothes dryers etc TERMS This warranty shall be...

Page 38: ......

Page 39: ......

Page 40: ...rchez dans la brochure les caract ristique de rendement nerg tique de foyer au gaz nerguide Selon CSA P 4 1 09 EFFICIENCY RATINGS Model EnerGuide Ratings Fire place Efficiency D O E AFUE CSDV30NV 65 4...

Reviews: