CSDV Series Direct Vent Gas Stove
VENTING INSTALLATION
VERTICAL TERMINATION CONFIGURA
-
TIONS
Figures 27 through 29 show four different configurations
for vertical termination.
IMPORTANT:
Install restrictor as indicated on chart
(Figure
13)
on Page 14.
V
H
1
H
ST1145
Vert vent 3 elbows
NOTE:
Install restrictor into 4" collar of stove or first vent section
as shown.
Figure 27 -
Vertical Rigid Venting Configuration using Three (3) 90°
Elbows with Two (2) Horizontal Runs
H
V
V
1
ST1146
vert vent 2 elbows
NOTE:
Install restrictor into 4" collar of stove or first vent section
as shown.
Figure 28 -
Vertical Rigid Venting Configuration using Two (2) 90°
Elbows
NOTE:
Vertical (V) + Vertical (V
1
) = 20' (6 m) Maximum
Table 5: Venting with Three (3) 90°
Elbows
Maximum Horizontal
(H+H
1
)
Minimum Vertical (V)
24" (610 mm)
52
1
⁄
2
" (1334 mm)
20' (6 m)
98
1
⁄
4
" (2495 mm)
Table 6: Venting with Two (2) 90°
Elbows
Maximum Horizontal
(H+H
1
)
Minimum Vertical (V)
24" (610 mm)
44
3
⁄
4
" (1137 mm)
20' (6 m)
98
3
⁄
4
" (2508 mm)