11
Defiant
®
1610CE Non-Catalytic Woodburning Stove
30003846
Summary of clearances
Minimum recommended side clearances to non-
combustible surfaces 125 mm (5”).
Minimum recommended rear clearance to noncom-
bustible surfaces 50 mm (2”).
NoTe:
The minimum thickness of solid noncombus-
tible materials is specified in section of Document ‘J’,
in relation to the clearance of the appliance from the
surface. As a general rule, the thickness of solid non-
combustible material forming the recess of a fireplace is
a minimum of 00 mm.
Minimum rear clearance from combustible walls
(e.g. timber framed or studded walls) 890 mm (35”)
measured from the rear edge of the stove top. (Fig.
11, b)
Minimum side clearance from combustible walls
610 mm (24”) measured from the side edge of the
stove top. (Fig. 11, a)
Minimum distance from stove to movable combus-
tible materials (e.g. furniture, drying clothes, etc.)
1220 mm (48”).
ST486a
Defiant EU
Clearance
Diagrams
10/06
A
B
ST486a
Fig. 11
Minimum clearances.
connecting Flue pipe - clearances
Single wall connecting fluepipes can reach extremely
high temperatures; therefore, clearances from the con-
necting fluepipe (chimney connector) must comply with
the requirements of Part J of Building Regulations 000
(Combustion Appliances and Fuel Storage Systems).
This can be achieved by following the recommenda-
tions of Approved Document ‘J’. These are as shown in
Figure 1.
34
FLUEPIPECLEARANCES
D
at least
3 x D
elevation
without
Shield
elevation
with Shield
at least
3 x D
at least
1.5 x D
at least 1.5
x D
plan without
Shield
plan with
Shield
Air space of at least 1 mm
between noncombustible shield
and combustible material
Fluepipe
at least
1.5 x D
at least
1.5 x D
at least 3 x D
D
at least
1.5 x D
ST911
Fig. 12
Connecting fluepipe clearances.