background image

12

WMC Series Woodburning Fireplace

20000583

FP593

SR/C

11/20/97

Fig. 19 

 Installing firestop spacer.

FP593

Nails (4)

Firestop Spacer

Joist

Attic Installation

Ceiling Installation

Joist

Firestop Spacer

Nails (4)

FP263

Fig. 20 

 Attic shield installlation (Canadian requirement).

IGF263

MBUF

5/9/96

Attic Insula-

tion Shield

Ceiling

Base 

Flanges

Nails

(4 required)

Attic Joist

If the area above the ceiling 

is

 an attic, position the firestop 

spacer with the flange on the top of the framed hole and 

the angled portion extending down into the hole.
Firestop spacers are not available for nor are they required 

on vertical walls.

DO NOT 

put any sealant around the area where the outer 

pipe slides through the firestop spacer.  If you seal this 

area, 

it may cause a fire hazard.

Canadian Requirements for

 Insulation Shield

In Canada, an attic insulation shield is required to prevent 

attic insulation from contacting the chimney section.  

NOTe:

 

If the attic insulation shield is used, the firestop is not re-

quired in the attic installation. Framing dimensions for the 

chimney hole should measure 14

Z\x

" x 14

Z\x

"  (368 x 368 

mm) for SK8; 17

Z\x

" x 17

Z\x

" (445 x 445 mm) for 3-wall.  An 

attic shield MUST be installed on top of attic joists (above 

the floor level).  (Fig. 20) 

NOTe:

 In the U.S., it is a good idea, although not always 

required, to install an attic insulation shield where blown-in 

insulation is planned to be used in the attic.
Install the attic insulation shield with the flanges on its base 

extending down into the framing hole. Nail each corner of 

attic insulation shield to the framing members of the ceil-

ing hole using 8d nails.  Attic shields are not required at 

the roof.

Continue Installing Pipe to Complete Run

Continue  attaching  pipe  sections  to  complete  system 

to next level always being careful that the pipe is firmly 

snapped locked in place before proceeding to next pipe 

section.

Chimney Supports

If  chimney  supports  are  required,  they  are  installed  the 

same as elbows.  Nail chimney support straps to adjacent 

structural framing, as shown on Page 7, Figure 7. Bend 

straps as necessary and make sure they are secure so 

they will support the weight of the chimney. A chimney sup-

port is 2

Z\x

" long when installed. Consider this dimension 

when  determining  how  many  straight  chimney  sections 

are needed.

NOTe:

  Chimney supports are generally used in long runs 

in a chase installation.

Additional Ceilings

If  you  encounter  additional  ceilings,  repeat  same  steps 

required for first ceiling installation.  Refer to firestop il-

lustration on Figure 19. 

Penetrating the Roof

Run  pipe  to  roof  line.    Since  chimney  system  must  be 

vented  to  the  out-of-doors,  you 

must 

use  an  approved 

termination.
If a chase is used, refer to the installation manual provided 

with the termination cap.

Locate Chimney Centerpoint On Roof

Use same procedure detailed in locating center point of 

the flue system.
Drive a nail up through roof at the center point.  This will 

determine center point on outside of the roof.

NOTe:

 If the attic insulation shield is used, the firestop is not 

required in the attic installation.

Summary of Contents for Royal Collection WMC36

Page 1: ...se in U S Canada Underwriter s Laboratories Report No MH7603 DO NOT DISCARD THIS MANUAL Retain for future use 20000583 1 13 Rev 31 FP583A WMC 12 18 98 WMC Series Woodburning Fireplaces Homeowner s Installation and Operating Manual ...

Page 2: ...t part not manufactured or approved by Vermont Cast ings Group in combination or assembly with a Vermont Castings Group fireplace system not withstanding any independent testing laboratory or other third party approval of such component parts or accessory Any such action may possibly cause a fire hazard Consult local building codes to ensure that you are in compliance before installing the firepla...

Page 3: ...ia 203mm 3 6 9 1 4 m m Fig 2 WMC42 Series specifications and framing FP592A WMC42 Series Woodburning Fireplace Circulating Model FP590A WMC36 SPECS 1 28 99 djt B 1 6 m m Z x 13mm Z x 36 914mm 35Z v 895mm 40 1016mm B 16mm 19C v 502mm 1C v 45mm 35Z x 902mm 21 7C v 197mm 7Z x 191mm Recessed Nailing Flange 11 Dia 279mm Rough Opening Width 41 Rough Opening Height Rough Opening Depth Gas Line Access 47 ...

Page 4: ...d Outlet Grille Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 pieces Inlet Grille Outside Air Cover Plate Electrical Access Gas Line Access both sides Nailing Flange Standoff Batt Insulation cut out around firestop Firestop Ceiling Level A B C FP1531 hearth dimensions 9 04 djt Front Width Back Width Depth A B C WMC36 33Z x 20Z v 18Z v 851 mm 514 mm 4...

Page 5: ... 1 0 0 1 0 31 60 0 1 0 1 0 34 65 0 0 2 0 0 37 70 1 1 0 1 1 41 77 0 0 1 1 1 45 83 0 1 2 0 1 47 87 0 0 0 2 1 51 94 0 1 1 1 1 53 98 0 0 3 0 1 56 103 0 1 0 2 1 59 108 0 0 2 1 1 62 113 0 1 3 0 1 64 117 0 0 1 2 1 68 124 0 1 2 1 1 70 128 0 0 0 3 1 74 134 0 1 1 2 2 78 140 0 0 3 1 2 81 146 0 1 0 3 2 84 151 0 0 2 2 2 87 156 0 1 3 1 2 89 160 0 0 1 3 2 93 166 0 1 2 2 2 95 170 0 0 0 4 2 99 177 0 1 1 3 2 101 18...

Page 6: ...t 2 609 mm above the peak of the roof but never less than 3 914 mm in height above the highest point where it passes through the roof 2 If a horizontal distance from the chimney to the peak of the roof is more than 10 3 m a chimney height refer ence point is established that is on the surface of the roof a distance of 10 3 m from the chimney in a horizontal plane The top of the chimney must be at ...

Page 7: ...mates If you live in a cold climate it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible Insulate base of fireplace with a noncombustible insula tion rated for a minimum of 300 F Insulating is very important for outside wall installations over a concrete slab If fireplace is installed on a platform insulation should b...

Page 8: ...uctions Read all instructions before beginning installation Follow instruc tions carefully The SCVS speed control may be used as an alternate wall switch in lieu of the single pole Listed 1 5 Amp 120V switch described in the fan or fireplace installation instruc tions Installation Instructions For mounting the speed control a 2 deep standard electri cal box should be used Using wire nuts supplied ...

Page 9: ...t Castings Group elbows Use the 30 Offset Elbow table on Page 5 to determine proper offset and parts required Each offset requires two 2 elbows The second elbow is equipped with support straps It is very important to install the second elbow in each offset as close to the ceiling or support as possible so the elbow straps can be secured to framing members to help support the weight of the chimney ...

Page 10: ...installing firestop spacer Size of Chimney Vertical 30 8 Flue SKFS2A SKFS6A SK Series 14 x 14 14 x 25 368mm x 368mm 368mm x 648mm 8 Flue FS2A FS6A S Series 3 Wall 17 x 17 17 x 29 445mm x 445mm 454mm x 753mm Angle of Chimney at Ceiling The inside dimension of the frame must be the same as the hole size selected from Figure 13 in order to provide required air space between the outside diameter of th...

Page 11: ... collar on top of the fireplace Install the pipe as pictured in Figure 17 When you get a good lock you will hear the pipe clearly snap together Once sections are snap locked in place it is extremely difficult to get them apart Make sure the pipe is firmly snapped and locked together as each pipe section is mounted When installing elbows only outer pipe will snap lock Middle pipes simply slide into...

Page 12: ...ld with the flanges on its base extending down into the framing hole Nail each corner of attic insulation shield to the framing members of the ceil ing hole using 8d nails Attic shields are not required at the roof Continue Installing Pipe to Complete Run Continue attaching pipe sections to complete system to next level always being careful that the pipe is firmly snapped locked in place before pr...

Page 13: ...ing Top Housing or Termination Follow the installation instructions provided with the chim ney termination you have selected Installing Chimney In a Chase Refer to Page 4 Figure 3 for an illustration of a typical chase installation CAUTION Treatment of firestop spacers and construc tion of chase may vary with type of building These instructions are not a substitute for local building codes You mus...

Page 14: ...otected with a specifically built wall shield as described below The special wall shield design described in Figure 19 is an alternate method of adding protection to side walls Rt must 1 85 minimum FP531b Fig 22 Mantel clearance FP531b mantel clearances 9 03 djt Z x 12 305mm Max 12 305mm Min 1Z x 38mm 6 159mm Min Combustible Mantel and Trim Finished Wall Header Standoff Noncombustible Material Gri...

Page 15: ...d from manufacturer of the material Factors are related by the formula K 1 R T given thickness R thermal resistance for a given thickness T K thermal conductivity Noncombustible material with a lower R value may be used provided thickness of material is sufficiently greater to maintain an equivalent total thermal resistance Rt Minimum Wall Clearances WITH Noncombustible Surround Facing WITHOUT Non...

Page 16: ...doffs Safety Strips Must be overlapped Z x minimum Hearth Extension Insulation Side View FP550 Fig 26 Sealing gaps How to Operate Your Fireplace Your fireplace can provide countless hours of pleasure and security However use your fireplace carefully because any time you build a fire inside a house a problem may develop Open Flue Damper The flue damper is meant to be closed only when the fire is co...

Page 17: ...to totally seal between the pipe and tube Note Gas pipe should not come in contact with any wood structures until it has reached a point at least one 1 inch away from fireplace side NOTE When installing an ANSI Z21 11 2 ventless appli ance the finishing materials used for the mantel must be rated at 250 F or greater BTU input of a gas appliance installed in fireplace should be rated less than 100 ...

Page 18: ...replace 26D0131 26D0131 5 Damper Knob Wood 7536177 7536177 6 Firebrick Left Side 3041104 3034102 7 Firebrick Back 3030102 3034104 8 Firebrick Right Side 3041105 3034103 9 Firebrick Hearth 3041103 3034105 10 Screen Rod two per fireplace 26D0138 61D0500 11 Top Brick Retainers three per fireplace 3030172 3030172 12 Cable Clips four per fireplace 7512135 7512135 13 O S A Assy 20003076 20003076 14a Doo...

Page 19: ...se an unapproved component to make any modifications you may create a possible fire hazard and will void the Vermont Castings Group warranty In ad dition such action may void the coverage provided by the owner s insurance Accessories Contact your Vermont Castings Group distributor or dealer for finishing Mantels available in a wide selection of styles Glass Door Optional Bi Fold door set Pewter fi...

Page 20: ...le chimney cap used to PLTSK8 SK8 terminate chimney through a chase Includes adapter Flashing not included Chase Top Housing Square chimney cap used to terminate chimney SLTSK8 SK8 through a chase Includes adapter Flashing not included SK8 Chimney Sections Pipe used to build 8 SK8 flue systems SK81 1 Long SK818 1 Long SK83 3 Long SK84 4 Long SK8 Chimney Elbows Elbow used to create an offset in an ...

Page 21: ...rom the chimney to combustible framing With 16 center lines Attic Insulation Shield Used to prevent attic insulation from FS2100 HT 3 wall CF 11 contacting the chimney system Canada Chimney Collar Enclosure Installs on the over the chimney collar of the CCE SK SK8 fireplace provides outside air to assist in cooling the chimney system Attic Insulation Shield Used to prevent insulation from coming i...

Page 22: ...22 WMC Series Woodburning Fireplace 20000583 ...

Page 23: ...ure dif ferentials produced by wind Broken glass components Cracks in ceramic and castable parts that do not affect safe operation We do not warrant this fireplace to be in compliance with your local building code Building codes vary greatly throughout the country and you should determine whether your local building code contains restrictions on the use of this fireplace before you purchase it Blo...

Page 24: ...Vermont Castings Group 149 Cleveland Drive Paris Kentucky 40361 www vermontcastingsgroup com ...

Reviews: