16
87D0058
SB50HB Series Woodburning Fireplace
FIrepLaCe INSTaLLaTION
LOCaTION SeLeCTION
Unpack and check the fireplace and chimney for dam-
age. If any items have been damaged, report this to your
dealer. Before beginning the installation, be sure you have
the proper parts in sufficient quantity. Refer to
Page 35
for
proper identification of parts.
Do not substitute parts. Use only parts listed for use with
the Model SB50HB fireplace.
FIrepLaCe INSTaLLaTION
1. Refer to Figure 1 for an example of a typical installation
of the fireplace components.
. Be sure the location of the fireplace will provide the re-
quired clearances indicated by
Figures 1, 3 & 4
and the
minimum chimney air space clearance to combustibles
of two inches.
3. Set the fireplace in the desired location and be sure
it is securely supported and leveled. Check the face
of the fireplace with a carpenter’s level and if it is not
plumb; correct it by placing shims under the edges of
the fireplace.
4. Block in the fireplace to prevent any shifting of the fire-
box. Secure the fireplace with nails or screws through
the flanges located on each side of the fireplace. Do not
enclose the fireplace until the combustion air duct and
chimney pipes are installed.
NOTe:
Some local codes may require electrically ground-
ing the fireplace and chimney.
CHIMNey INSTaLLaTION
In order to assure safe and satisfactory performance of the
fireplace, it is very important to properly install the chimney.
This is an important part of the installation and the sections
of this manual pertaining to chimney installation should be
reviewed very thoroughly.
For your safety, some of the important things to remember
in regard to chimneys are listed below:
1. Use only parts and accessories labeled for use with this
fireplace.
. Use only undamaged parts and accessories.
3. Enclose the chimney where it passes through the living
spaces to prevent contact with and possible damage to
the chimney.
4. Install firestop spacers at each ceiling level.
5. Install the proper chimney cap or chimney housing on
the chimney to prevent the entry of rain and debris
into the chimney and to assure the proper venting of
smoke.
6. Do not use more than four elbows in the chimney.
NOTe:
To select the proper chimney height, refer to
Figure
3
. The flue outlet must be a minimum of three feet above
the highest point where the chimney penetrates the roof
and a minimum of two feet above all portions of the build-
ing within ten feet. If the chimney is to include elbows to
offset the chimney, refer to the Chimney Offset and Cap
Installation section of this manual. There must be at least
two inches air space between all sections of the chimney
and combustible materials between floors.