ALARM TYPE SELECTION 

 

A1FU/A2FU 

ALARM TYPE 

ALARM OUTPUT OPERATION 

 

Alarm function OFF 

Output OFF 

 

PV high alarm 

                                                             

                 

                          PV 

  SP 

 

PV low alarm 

                                       

                   

                          PV 

                                    SP 

 

Deviation high alarm 

                                                             

                 

                        PV 

  SP+ALSP 

 

Deviation low alarm 

                                         

                 

                        PV 

 SP+ALSP 

 

Band high alarm 

                                    OFF                   

           

     

     

              PV 

SP-ALSP   SP   SP+ALSP 

 

Band low alarm 

                    OFF                        OFF   

           

     

     

              PV 

SP-ALSP   SP   SP+ALSP 

 

PV high alarm with delay time 

                      ALdt                       

 

         

                      PV 

                ALSP     

 

PV low alarm with delay time 

                     

  ALdt     

 

             

                    PV 

              ALSP     

 
ALARM SPECIAL FUNCTION SELECTION 
 

ALMD DESCRIPTION 

 

Normal alarm mode 

 

Startup inhibit

    When selected, in any alarm function, prevents an alarm on power up. 

The alarm is enabled only when the process value reaches the alarm set point for the first 
time and is used to avoid alarm trips during startup.

 

 

Latch mode. 

When selected, the alarm output and indicator latch as the alarm occurs. The 

alarm output and indicator will be energized even if the alarm condition has been cleared 
and will only reset when the power to the controller is switched off..

 

 

Standby and latch mode 

 

99Hours 59 Minutes 

 

99Minutes 59Seconds 

 
 

 

10

Summary of Contents for VD 26 Series

Page 1: ...the parameters including the Process Variable and Set Point It is fully configurable on input including PT100 RTD There are three simple steps required to get you up and running 1 Installation 2 Wiri...

Page 2: ...play will change and read Type 5 Use the up or down keys to select the input type you require 6 Now press the set key once and the display will read Type 7 Now press the set key a few times until you...

Page 3: ...ill be charged for repairing it 6 2 All controllers are Relay output as factory standard To have SSR you must especially order them with this option 7 Relay output If you are using a relay output cont...

Page 4: ...w Scale of Linear Input 1999 9999 199 9 999 9 0 0 High Scale of Linear Input 1999 9999 199 9 999 9 100 0 10 Commissioning Having correctly wired the unit you are now ready for the initial turn on 1 Tu...

Page 5: ...e next programmable parameter press for 5 seconds to move from one programming level to next 2 UP KEY Press to increase the set point or parameter value 3 DOWN KEY Press to decrease the set point or p...

Page 6: ...PROGRAMMING LEVEL PARAMETERS lst Prog Level 2nd Prog Level 3rd Prog Level Press 5 seconds Press 5 seconds Press 5 seconds 6...

Page 7: ...ON OFF control mode 0 0 300 0 0 0 Derivative Rate This value is automatically calculated by activating the Auto tune function When 0 0 this parameter will not appear 0 900sec 0 Hysteresis for ON OFF...

Page 8: ...000 58 1832 B 0 1800 32 3272 R 50 1750 58 3182 S 50 1750 58 3182 N 50 1300 58 2372 C 50 1800 58 3272 D PT 200 850 328 1652 J PT 200 600 328 1112 LINE 1999 9999 Refer to figure K Unit of process value...

Page 9: ...efer to alarm function section for detail nonE Hi Lo dif H dif L bd Hi bd Lo t on t oFF Alarm 3 mode Refer to alarm mode section for detail nonE Stdy Lath St La HH mm mm SS RS485 address 0 255 0 Commu...

Page 10: ...CTION SELECTION ALMD DESCRIPTION Normal alarm mode Startup inhibit When selected in any alarm function prevents an alarm on power up The alarm is enabled only when the process value reaches the alarm...

Page 11: ...ck correct input sensor selection Sensor break error Sensor not connected Replace sensor Check the sensor is connected correctly Keypad no function Keypads are locked Keypads defective Set to a proper...