Communication
Silkprint
Port Name
Pin No
Pin Name
Meaning
Remarks
J14
2
Output dry
contact and
REPO port
5
Summary_
Alarm_A
System Alarm (default) /On Battery
/Battery Low Capacity /UPS
Fault / On Bypass / UPS /Remote
EPO / Main input abnormal / On
Maintenance Bypass / Load Shed
Signal 1 / Load Shed Signal 2 /
Internal MBB Closed.
Pin5 and Pin7 shorted for alarm
state.
Note: We recommend adopting
the switch with normally-closed
auxiliary contact when load shed
signal is selected
Configurable
input dry
contact J14-
5/7
7
Summary_
Alarm_B
2
REPO_NC
Trigger EPO upon Pin2 and Pin4
opened
4
+12V_EPO
6
+12V_EPO
Trigger EPO upon Pin6 and Pin8
shorted
8
REPO_NO
J15
2
Battery BCB
port
1
BCB_DRIVE
BCB tripping drive, normally 0V, 12V
tripping
2
BCB_STATUS
BCB switch status signal
3
GND_SELV
GND
4
BCB_ONLINE
BCB on line
J16
3
Rectifier back-
feed output port
1
MFP_O
Rectifier back-feed normally open
contact. Closed when there is
rectifier back-feed
2
MFP_S
Rectifier back-feed common
contact
3
MFP_C
Rectifier back-feed normally
closed contact. Open when there is
rectifier back-feed
J17
3
Bypass back-
feed output port
1
BFP_O
Bypass back-feed normally open
contact. Closed when there is
bypass back-feed
2
BFP_S
Bypass back-feed common contact
3
BFP_C
Bypass back-feed normally closed
contact. Open when there is bypass
back-feed
Summary of Contents for EXS 0080kTK16FN01000
Page 1: ...Liebert EXS 80kVA UPS User Manual...
Page 8: ...This page is intentionally left blank...
Page 46: ...Vertiv Liebert EXS 80kVA UPS User Manual 32 This page is intentionally left blank...
Page 66: ...Vertiv Liebert EXS 80kVA UPS User Manual 52 This page is intentionally left blank...
Page 102: ...Vertiv Liebert EXS 80kVA UPS User Manual 88 This page is intentionally left blank...
Page 112: ...Vertiv Liebert EXS 80kVA UPS User Manual 98 This page is intentionally left blank...
Page 116: ...Vertiv Liebert EXS 80kVA UPS User Manual 102 This page is intentionally left blank...
Page 124: ...Vertiv Liebert EXS 80kVA UPS User Manual 110 This page is intentionally left blank...
Page 128: ...Vertiv Liebert EXS 80kVA UPS User Manual 114 This page is intentionally left blank...
Page 134: ...Vertiv Liebert EXS 80kVA UPS User Manual 120 This page is intentionally left blank...
Page 136: ...Vertiv Liebert EXS 80kVA UPS User Manual 122 This page is intentionally left blank...