Vertiv | Liebert EXS 80kVA UPS | User Manual
30
Electrical Installation
Connection of system input
1.
3-in 3-out, common input configuration (default)
Connect the main input terminals (mA-mB-mC-N) and bypass input terminals (bA-bB-bC-N), and then
parallely connect them to the main input terminals as shown in
. Ensure correct phase rotation.
The shorting cables of common input configuration were assembled before delivery, no need to reinstall
them again.
2.
3-in 3-out, split bypass configuration
Remove the bypass input cables (bA-bB-bC) connected to the main input terminal. Connect the bypass
input cables to the bypass input terminal (bA-bB-bC). Ensure correct phase rotation. Ensure that the main
input cables (mA-mB-mC) are connected to the main input terminal correctly and reliably.
Connection of system output
Connect the system output cables between the output terminals (oA-oB-oC-N) in the cabinet and the load.
Refer to
for the torque value. Ensure correct phase rotation.
Warning
If there is no requirement of power supply for the load before arrival of the service engineer, ensure that the system out-
put cables are safely isolated at their ends.
Connection of batteries
If external batteries are required, ensure correct polarity of the connections from the battery string terminals to
the BCB and from the BCB to the battery input terminals (+, N, -) in the UPS cabinet (see
), i.e., (+) to
(+) and (-) to (-), (N) to (N), and disconnect one or more battery cell links in each tier. Do not reconnect these
links and do not close the BCB before authorized to do so by the service engineer.
•
When connecting the cables between external battery terminals and BCB, the connection should
begin from the BCB terminal.
Summary of Contents for EXS 0080kTK16FN01000
Page 1: ...Liebert EXS 80kVA UPS User Manual...
Page 8: ...This page is intentionally left blank...
Page 46: ...Vertiv Liebert EXS 80kVA UPS User Manual 32 This page is intentionally left blank...
Page 66: ...Vertiv Liebert EXS 80kVA UPS User Manual 52 This page is intentionally left blank...
Page 102: ...Vertiv Liebert EXS 80kVA UPS User Manual 88 This page is intentionally left blank...
Page 112: ...Vertiv Liebert EXS 80kVA UPS User Manual 98 This page is intentionally left blank...
Page 116: ...Vertiv Liebert EXS 80kVA UPS User Manual 102 This page is intentionally left blank...
Page 124: ...Vertiv Liebert EXS 80kVA UPS User Manual 110 This page is intentionally left blank...
Page 128: ...Vertiv Liebert EXS 80kVA UPS User Manual 114 This page is intentionally left blank...
Page 134: ...Vertiv Liebert EXS 80kVA UPS User Manual 120 This page is intentionally left blank...
Page 136: ...Vertiv Liebert EXS 80kVA UPS User Manual 122 This page is intentionally left blank...