Vertiv | Liebert EXS 80kVA UPS | User Manual
49
Operator Control and Display Panel
Table 4-7 UPS Prompt Message List
Fault
Meaning
Rectifier in Setting
The rectifier starts up and is in synchronization
Inverter in Setting
The inverter starts up and is in synchronization with the monitoring
Battery Reset
The battery state restores to a new one
Battery End of Discharge
Inverter turned off due to battery EOD
BCB Closed
BCB state (closed)
Charger Shutdown
Dry contact signal. When the dry contact gives a command of charger shutdown, then
the charger will shut down
Fault Clear
Select the command of ‘Clear faults’ via the Control page
Silence Active
Select the command of ‘Mute/Unmute audible alarm’ via the Control page
Silence Inactive
Under conditioner of buzzer silence, select the ‘Mute/Unmute audible alarm’ command
via the Control page
Inverter Manual On
Power button on the operator control and display panel pressed to manually turn on the
inverter
Turn On Fail
When the Inverter Manual On is pressed, the inverter failed to turn on. This may be the
result of an invalid operation (maintenance bypass switch closed) or DC bus or rectifier
that is not ready
Inverter Manual Off
Power button on the operator control and display panel pressed manually to turn off the
inverter
Autostart
After UPS shutdown at EOD, the inverter automatically starts upon mains restoration
Load on Bypass
UPS is in bypass mode
Load on Inverter
UPS is in normal mode
Load on Battery
UPS is in battery mode
Load Off
UPS shut down, both bypass and inverter have no output
Automatic Battery Test
The battery is under automatic periodic battery maintenance discharge test (20%
capacity discharge)
Calibrated Battery Test
The user initiates a battery capacity test (100% capacity discharge)
Manual Battery Test
The user initiates a maintenance test (20% capacity discharge)
Rectifier DSP Update
Rectifier DSP software being updated
Inverter DSP Update
Rectifier
FPGA software being updated
Inverter FPGA Update
Inverter DSP software being updated
Monitor Update
Inverter FPGA software being updated
Remote Turn On
Turn on the inverter through the service command
Remote Turn On Fail
Caused by invalid operation (maintenance bypass switch closed), DC bus or rectifier not
ready
Remote Turn Off
Turn off the inverter through the service command
Flash Operate Fail
Historical record not saved
Summary of Contents for EXS 0080kTK16FN01000
Page 1: ...Liebert EXS 80kVA UPS User Manual...
Page 8: ...This page is intentionally left blank...
Page 46: ...Vertiv Liebert EXS 80kVA UPS User Manual 32 This page is intentionally left blank...
Page 66: ...Vertiv Liebert EXS 80kVA UPS User Manual 52 This page is intentionally left blank...
Page 102: ...Vertiv Liebert EXS 80kVA UPS User Manual 88 This page is intentionally left blank...
Page 112: ...Vertiv Liebert EXS 80kVA UPS User Manual 98 This page is intentionally left blank...
Page 116: ...Vertiv Liebert EXS 80kVA UPS User Manual 102 This page is intentionally left blank...
Page 124: ...Vertiv Liebert EXS 80kVA UPS User Manual 110 This page is intentionally left blank...
Page 128: ...Vertiv Liebert EXS 80kVA UPS User Manual 114 This page is intentionally left blank...
Page 134: ...Vertiv Liebert EXS 80kVA UPS User Manual 120 This page is intentionally left blank...
Page 136: ...Vertiv Liebert EXS 80kVA UPS User Manual 122 This page is intentionally left blank...