Vertiv | Liebert EXS 80kVA UPS | User Manual
59
UPS Operating Instructions
Figure 5-7 Flow Page on Bypass
In Inverter mode, press the power button. If the bypass is abnormal, then the interface shown in
is
displayed, select ‘NO’ to shut down the UPS output.
Figure 5-8 Bypass Abnormal Interface
5.3.3. Transfer from Bypass Mode to Normal Mode
In Bypass mode, press the power button, and the LCD prompts a dialogue box, as shown in
. After
selecting ‘YES’, the inverter executes self-check and start-up. After the inverter runs normally, the UPS will
transfer to normal mode, and the run indicator will be solid on.
Summary of Contents for EXS 0080kTK16FN01000
Page 1: ...Liebert EXS 80kVA UPS User Manual...
Page 8: ...This page is intentionally left blank...
Page 46: ...Vertiv Liebert EXS 80kVA UPS User Manual 32 This page is intentionally left blank...
Page 66: ...Vertiv Liebert EXS 80kVA UPS User Manual 52 This page is intentionally left blank...
Page 102: ...Vertiv Liebert EXS 80kVA UPS User Manual 88 This page is intentionally left blank...
Page 112: ...Vertiv Liebert EXS 80kVA UPS User Manual 98 This page is intentionally left blank...
Page 116: ...Vertiv Liebert EXS 80kVA UPS User Manual 102 This page is intentionally left blank...
Page 124: ...Vertiv Liebert EXS 80kVA UPS User Manual 110 This page is intentionally left blank...
Page 128: ...Vertiv Liebert EXS 80kVA UPS User Manual 114 This page is intentionally left blank...
Page 134: ...Vertiv Liebert EXS 80kVA UPS User Manual 120 This page is intentionally left blank...
Page 136: ...Vertiv Liebert EXS 80kVA UPS User Manual 122 This page is intentionally left blank...