SAG582136800
System Application Guide
Revision BA, April 8, 2020
Spec. No. 582136800 (Model 502
NGFB
)
Page 2 of 129
•
Assembled Shelves with Rear AC Input, Configured for GMT Distribution Panel and Top DC
Distribution Cabinet
List
No.
19” or 23”
Relay Rack
Mounting
Number of
Power Shelves
No. of Rectifier
Mounting Positions
Output
Capacity
(Amperes)
20
19”
1 (Main)
4
See Table 6
21
19”
2 (Main and Expansion)
9
22
23”
1 (Main)
5
23
23”
2 (Main and Expansion)
11
26
19”
3 (1 Main, 2 Expansion)
14
27
23”
3 (1 Main, 2 Expansion)
17
Table 5
•
Output Capacities
List
No.
208/240VAC Input
120VAC Input
+40°C
+65°C
+40°C
+65°C
1
166A
133A
105A
84A
2
208A
166A
131A
105A
3
208A
166A
131A
105A
4
250A
200A
157A
126A
5
166A
133A
105A
84A
6
374A
299A
236A
189A
7
208A
166A
131A
105A
8
400A*
365A
290A
230A
10
166A
133A
105A
84A
11
374A
299A
236A
189A
12
208A
166A
131A
105A
13
458A
366A
288A
231A
14
208A
166A
131A
105A
15
250A
200A
157A
126A
16
582A
400A
367A
294A
17
600A
400A
445A
357A
20
166A
133A
105A
84A
21
374A
299A
236A
189A
22
208A
166A
131A
105A
23
458A
366A
288A
231A
26
582A
400A
367A
294A
27
600A
400A
445A
357A
* - Maximum busbar capacity.
Table 6