SAG582136800
System Application Guide
Revision BA, April 8, 2020
Spec. No. 582136800 (Model 502
NGFB
)
Page 30 of 129
5)
Specify the batteries you intend to use with each List 93 ordered. Lugs for battery connections vary according
to the batteries to be installed. Battery cables will be lugged as shown in the Table E. The table is provided for
reference only.
Note:
If battery model is
not
specified, lugs will
not
be installed at factory. Instead, both available lug kits for the
furnished wire size will be shipped loose with the order.
6)
Specify with or without tray-mounted battery disconnect circuit breakers.
Note:
All List 93 trays in a rack will be furnished with or without battery disconnect circuit breakers as specified for the
first tray ordered.
7)
If ordering List 93 with tray-mounted circuit breakers, order one (1) breaker per List 93 from Table F.
8)
If ordering List 93 with tray-mounted circuit breakers, specify breaker mounting on left or right side of tray. Circuit
breaker mounting kits shown in the Table F will be installed. Kit numbers are provided for reference only.
9)
If ordering List 93 with tray-mounted circuit breakers, order Alarm Jumper P/N 524384 for each system to connect the
alarm terminal of up to three (3) battery disconnect circuit breakers.
Battery Tray P/N 559806
Manufacturer*
Model
Vertiv
P/N
Rated 8-Hr.
Capacity
(Ah)
Dimension
W x L x H
(Inches)
Required
Tray
Spacing
Weight
(per
battery)
(lbs)
Northstar
NSB110FT
--
110
4.92 X 22.05 X 8.94
7U
91
Northstar
NSB170FT
--
167
4.92 X 22.05 X 12.60
8U
131
Deka Unigy I
12AVR-150ET
122018
150
4.90 X 22.00 X 11.75
8U
115
C&D
TEL12-210F
554579
202
4.90 X 22.00 X 12.80
8U
132
Douglas
DGS12-150F
125453
150
4.90 X 22.00 X 12.70
8U
137
Douglas
DSN12-170F
--
170.8
4.92 X 22.05 X 12.60
8U
130
* See
Battery Manufacturer Information
located at the end of this document.
Table A