List KG: 19”/23” 20-Position GMT Fuse Panel (P/N 545590)
Features
♦
1U-high GMT fuse panel that provides Single Load Distribution (-48V).
♦
Provides twenty (20) 0A to 15A GMT fuse load distribution positions.
Caution: At +40°C and +65°C ambient, a fuse with a rating of greater than 10 amperes SHALL HAVE an empty mounting
position between it and any other fuse.
♦
Maximum Capacity: 80A @ +40°C and 80A @ +65°C.
♦
Can be mounted in 19” or 23” racks.
♦
Factory mounted and connected when ordered with power system.
♦
If the Distribution Cabinet in the system is equipped with Low Voltage Load Disconnect (LVLD), all List KG loads are
unaffected by the LVLD.
♦
If one or more distribution fuses opens, one set of Form-C relay contacts changes state, and resistive battery is provided
to an alarm terminal. Alarm circuit is factory connected to activate the Power System Controller fuse alarm.
Restrictions
Available only in List 20, 21, 22, 23, 26 and 27 systems.
Ordering Notes
1)
Order one (1) List KG for each List 20, 21, 22, 23, 26 or 27 system ordered.
2)
Order fuses, as required, per Table 9.