SAG582136800
System Application Guide
Revision BA, April 8, 2020
Spec. No. 582136800 (Model 502
NGFB
)
Page 80 of 129
19” Termination Panel Kit (P/N 555234)
Features
♦
Provides a termination panel that is mounted into a 19.4” (493mm) wide rack rail of a Knurr Data Cabinet.
♦
Ten (10) termination points (1/4-20 x 0.875” studs on 0.625” centers) per polarity provided for PDU and power shelf
connections.
♦
Pre-terminated cables available for connection from termination panel to power shelf output terminals.
♦
Removable center link provided in each polarity.
Restrictions
For use with List 1 and List 2 only.
Ordering Notes
1)
Order a 19” Termination Panel, P/N 555234, as required.
2)
Order rectifier shelf cables as required.
•
P/N 555232: One (1) 24” long, 2/0 AWG, cable provided for each polarity. Two-hole lug (3/8” clearance holes on 1”
centers) for power shelf connection. Two-hole lug (1/4” clearance holes on 5/8” centers) for termination panel
connection. For use with 582136800 List 1.
•
P/N 555233: One (1) 24” long, 4/0 AWG, cable provided for each polarity. Two-hole lug (3/8” clearance holes on 1”
centers) for power shelf connection. Two-hole lug (1/4” clearance holes on 5/8” centers) for termination panel
connection. For use with 582136800 List 2.
•
P/N 556440: One (1) 24” long, 2/0 AWG, cable provided for each polarity. Two-hole lug (3/8” clearance holes on 1”
centers) for power shelf connection. Two-hole 90-degree lug (1/4” clearance holes on 5/8” centers) for termination
panel connection. For use with 582136800 List 1.
•
P/N 556441: One (1) 24” long, 4/0 AWG, cable provided for each polarity. Two-hole lug (3/8” clearance holes on 1”
centers) for power shelf connection. Two-hole 90-degree lug (1/4” clearance holes on 5/8” centers) for termination
panel connection. For use with 582136800 List 2.