System Application Guide
SAG582136800
Spec. No. 582136800 (Model 502
NGFB
)
Revision BA, April 8, 2020
Page 81 of 129
M6 Mounting Hardware
Torque to 88.5 in-lbs.
Removable
Link
Removable
Link
Connection Points for
PDU and Power Shelf
(10 per polarity).
Torque to 75 in-lbs.
P/N 555234
Termination Assembly
Cable Assemblies
Cover
P/N 555232
One (1) 24” long, 2/0 AWG,
cable provided for each polarity.
Two hole lug (3/8” clearance holes on 1” centers)
for power shelf connection.
Two hole lug (1/4” clearance holes on 5/8” centers)
for termination panel connection.
For use with 582136800 List 1.
P/N 556441
One (1) 24” long, 4/0 AWG,
cable provided for each polarity.
Two hole lug (3/8” clearance holes on 1” centers)
for power shelf connection.
Two hole 90-degree lug (1/4” clearance holes on 5/8” centers)
for termination panel connection.
For use with 582136800 List 2.
P/N 556440
One (1) 24” long, 2/0 AWG,
cable provided for each polarity.
Two hole lug (3/8” clearance holes on 1” centers)
for power shelf connection.
Two hole 90-degree lug (1/4” clearance holes on 5/8” centers)
for termination panel connection.
For use with 582136800 List 1.
P/N 555233
One (1) 24” long, 4/0 AWG,
cable provided for each polarity.
Two hole lug (3/8” clearance holes on 1” centers)
for power shelf connection.
Two hole lug (1/4” clearance holes on 5/8” centers)
for termination panel connection.
For use with 582136800 List 2.
19
.1
2
18.335