SAG582136800
System Application Guide
Revision BA, April 8, 2020
Spec. No. 582136800 (Model 502
NGFB
)
Page 90 of 129
Input
Voltage
(VAC)
Ambient
Operating
Temp.
(1)
Max. Total
Output Curr.
(Amps)
Loop
Length (Ft.)
1.0 Volt Drop
(2)
Recm. 90°C
Wire Size
Recm.
Crimp Lug
(3)
120
40
105
45
(2) 6 AWG
(2) 245349900
56
(1) 2 AWG
(1) 245348200
90
(1) 1/0 AWG
(1) 245347100
65
84
56
(2) 6 AWG
(2) 245349900
89
(2) 4 AWG
(2) 245350000
113
(1) 1/0 AWG
(1) 245347100
240
40
166
57
(1) 2/0 AWG
(1) 245347200
91
(1) 3/0 AWG
(1) 245347300
114
(2) 1/0 AWG
(2) 245347100
65
133
89
(2) 2 AWG
(2) 245348200
143
(2) 1/0 AWG
(2) 245347100
Table 14A
Recommended DC Output Wire Size PER SHELF and Lug Selection
LISTS 1 and 5
Input
Voltage
(VAC)
Ambient
Operating
Temp.
(1)
Max. Total
Output Curr.
(Amps)
Loop
Length (Ft.)
1.0 Volt Drop
(2)
Recm. 90°C
Wire Size
Recm.
Crimp Lug
(3)
120
40
131
36
(2) 6 AWG
(2) 245349900
72
(1) 1/0 AWG
(1) 245347100
91
(1) 2/0 AWG
(1) 245347200
65
105
114
(1) 2/0 AWG
(1) 245347200
144
(1) 3/0 AWG
(1) 245347300
181
(2) 1/0 AWG
(2) 245347100
240
40
208
57
(2) 2 AWG
(2) 245348200
91
(2) 1/0 AWG
(2) 245347100
114
(2) 1/0 AWG
(2) 245347100
144
(2) 2/0 AWG
(2) 245347200
Table 14B
Recommended DC Output Wire Size PER SHELF and Lug Selection
LISTS 2, 3 and 7