SAG582136800
System Application Guide
Revision BA, April 8, 2020
Spec. No. 582136800 (Model 502
NGFB
)
Page 104 of 129
Remote Shunt Connections (Lists 5 – 8)
Nominal
Input Voltage
40°C Ambient
65°C Ambient
Max.
Output
Current
(Amps)
90C°
Cable Size
Max. Loop
Length at
.4V Drop
(Ft.)
65C Output
Current
(Amps)
90C°
Cable Size
Max. Loop
Length at
.4V Drop
(Ft.)
208/240VAC
List 5
166.6
2 AWG
12.3
133.3
1/0 AWG
24.5
List 6
374.9
250 kcmil
20.6
300
350 kcmil
36.1
List 7
208.3
1/0 AWG
15.7
166.6
2/0 AWG
24.7
List 8
400
250 kcmil
19.3
366.6
500 kcmil
42.2
120VAC
List 5
105.1
4 AWG
12.3
84.1
2 AWG
24.4
List 6
236.6
1/0 AWG
13.8
189.3
3/0 AWG
27.4
List 7
131.4
2 AWG
15.5
105.2
2 AWG
19.5
List 8
289.2
4/0 AWG
22.7
231.4
4/0 AWG
28.3
Notes:
1. The shunt connected to these terminals must be connected to the output cables of this plant within these maximum
distances for the cable sizes used. Loop length is the sum of the lengths of the positive and negative leads.
2. Wire sizes are based on recommendations of the American National Standards Institute (ANSI) approved National
Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-17 for wire rated at 90°C conductor
temperature operating in ambient temperatures of 40°C and 65°C was used.
Table 17
Cable Sizes