SPECIFICATIONS
1.
SYSTEM
1.1
Environmental Ratings
1.1.1
Operating Ambient Temperature Range:
(A)
-40°C (-40°F) to +65°C (+149°F) with derating output.
(B)
-40°C (-40°F) to +40°C (+104°F) with full power performance.
1.1.2
Storage Ambient Temperature Range: -40°C (-40°F) to +80°C (+176°F).
1.1.3
Humidity: This Power System is capable of operating in an ambient relative humidity range of 0% to 93%, non-
condensing.
1.1.4
Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m).
1.1.5
Mounting: This product is intended only for installation in a Restricted Access Location on or above a non-
combustible surface.
This product must be located in a Controlled Environment with access to Crafts persons only.
This product is intended for installation in Network Telecommunication Facilities (CO, vault, hut, or other
environmentally controlled electronic equipment enclosure).
This product is intended to be connected to the common bonding network in a Network Telecommunication
Facility (CO, vault, hut, or other environmentally controlled electronic equipment enclosure).
Typical industry standards recommend minimum aisle space clearance of 2'6" for the front of the relay rack
and 2' for the rear of the relay rack.
Separate shelves are available for mounting in either a 19" or 23" wide relay rack (1” or 1-3/4” multiple drilling).
Mounting angles are positioned for a 5-inch front projection mounting only.
1.1.6
Ventilation Requirements: Rectifier and mounting shelf ventilating openings must not be blocked and
temperature of air entering rectifiers must not exceed rated Operating Ambient Temperature Range stated above.
1.2
Compliance Information
1.2.1
Safety Compliance:
(A)
Spec. Nos. 58213680001, 58213680002, 58213680003, 58213680004, 58213680014, 58213680015: This
unit meets the requirements of UL 60950, Standard for Information Technology Equipment, and is UL
Recognized as a power supply for use in Telephone, Electronic Data Processing, or Information Processing
Equipment. This unit also meets the requirements of CAN/CSA 22.2, No. 60950-00 and is tested and Certified
by UL ("c UR") as a Component Type Power Supply.
(B)
Spec. No. 58213680005, 5821368006, 58213680007, 5821368008, 58213680010, 5821368011,
58213680012, 5821368013, 58213680016, 5821368017, 5821368020, 58213680021, 5821368022,
58213680023, 58213680026, 58213680027: This power distribution system is UL LISTED as a DC Power
Distribution Center for Communications Equipment and meet the requirements of UL 60950-1; 2003 and UL
subject 1801 and meets the requirements of Canadian Standard C22.2 No. 225-M90 Telecommunications
Equipment and C22.2, No. 60950-1-03 (cULus).