SAG582136800
System Application Guide
Revision BA, April 8, 2020
Spec. No. 582136800 (Model 502
NGFB
)
Page 28 of 129
List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167
Features
♦
Provides four (4) sets of hardware for anchoring the relay rack to the floor.
Ordering Notes
1)
Order as required.
List 90: Optional Temperature Probe, 12-Ft. Total Cable Length
Features
♦
Up to two (2) temperature probes can be connected to the Customer Interface (IB2) Board. Either or both probes can be
programmed to monitor ambient temperature or
battery temperature.
♦
A temperature probe set as a battery probe can
also be designated to be used for the battery
charge temperature compensation feature. If the system is equipped with the ACU+ or NCU Controller, the battery
charge temperature compensation feature can be programmed to use one probe or the average or highest value of all
probes programmed to monitor battery temperature. The battery charge temperature compensation feature allows the
controller to automatically increase or decrease the output voltage of the system to maintain battery float current as
battery temperature decreases or increases, respectively. Battery life can be extended when an optimum charge voltage
to the battery with respect to temperature is maintained.
♦
If the system is equipped with the ACU+ or NCU Controller, a temperature probe set as a battery probe can also be used
for controlling against battery thermal runaway (BTRM feature).
♦
The Temperature Probe assembly consists of two pieces that plug together to make a complete probe. When ordered,
P/N 04118246 (3 feet long) is pre-wired to the shelf. P/N 04118247 (9 feet long) is shipped loose. Total length: 12 ft.
Restrictions
A temperature probe programmed to monitor battery temperature should be mounted on the top or side of a battery cell to
sense battery temperature. A temperature probe used for battery charge temperature compensation or BTRM (Battery
Thermal Runaway Management) should also be mounted on the top or side of a battery cell. A temperature probe
programmed to monitor ambient temperature should be mounted in a convenient location, away from direct sources of heat
or cold.
Ordering Notes
1)
Requires IB2 Interface Board (not included as standard in Lists 1, 3, 5, 6, 7 and 8).
2)
Order up to two (2) Temperature Probes for each system, as required. (Each List 90 includes one (1) P/N 04118246 and
one (1) P/N 04118247, and together makes up one temperature probe.)
3)
Only one (1) Temperature Probe can be used for compensation (in the SCU+). If multiple probes are required, order (1)
SM-TEMP Temperature Concentrator.
4)
See “Optional Temperature Probes” on page 68 for temperature probe options with a mounting tab.